Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Supply Voltage | 15 to 260 VAC or VDC |
Max Supply Voltage | 280VAC or 300VDC |
Power Consumption | 1.5 watts max. |
Transient Protection | 2500 V for 10ms |
Setpoint Stability | ± 1% |
Response Time | 1 sec ON / 100ms OFF |
Reset Type | Automatic |
Dead Band | less than 5% all ranges |
Contact Rating | SPDT 10A at 240VAC resistive |
Expected Relay Life | Mech: 10 million operations Elec: 100,000 at rated load |
Operating Temperature | -13º to +122º F |
Humidity Tolerance | 0-97% without condensation |
Enclosure Material | ABS plastic |
Mounting | 8-pin socket (*order separately) |
Series Features |
MODEL 2628 AC/DC Voltage Monitor |
Series Description: The Model 2628 AC/DC Voltage Monitor is designed to continuously monitor any AC or DC voltage from 15 to 260 volts. Input voltages below the set-point cause the output contacts to de-energize. Input voltages above the set-point cause the output contacts to energize. The dead band between pull-in and drop-out is less than 5%. Dip switches are used on the Model 2628 to choose between AC and DC voltage monitoring, and to select one of the eight trip level ranges. Each trip level has a 35 voltage range, with a 5 volt overlap between the ranges. The unit has a screwdriver adjustment to set the exact trip point within that 35 volt range. |
|