Product Description
Description: Voltage Monitor Relay • Type: Under Voltage • Coil Voltage: 120 VAC • Contact Configuration: DPDT (2 Form C) • Mounting: Base • Contact Current: 10 Amps
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Function | Voltage Sensor |
Nominal input voltage | 120VAC |
Max. input voltage | 135VAC |
Frequency | 60Hz |
Power consumption | 2 watts max. |
Drop-out voltage | 80VAC |
Pick-up voltage | 84VAC |
Repeat accuracy | ± 1% (fixed conditions) |
Repeat accuracy | ± 2% (0°-140° F) |
Output | DPDT 10A at 240VAC resistive |
Expected relay life | Mechanical: 10 million operations Electrical:100,000 oper at rated load |
Reset | Automatic |
Response time | 28.3ms max. |
Reset time | 10 seconds |
Operating temperature | - 20o to +140o F |
Humidity tolerance | 0-97% without condensation |
Case material | ABS plastic |
Weight | 9.4 oz. |
Series Features |
MODEL 2602 Voltage Sensor |
Series Description: The Model 2602 Voltage Sensor is a rapid response device for sensing a low voltage condition on 120VAC, 60Hz, single phase power systems. Operating power is drawn from the same line being monitored. Upon sensing a voltage below 80VAC, the internal relay, which is energized under normal operating conditions, will drop out. The solid-state sensor will respond in one-half of an AC cycle (8.33ms.), plus the flight time of the relay (20ms. max.). When the voltage rises above 84VAC, an internal 10-second timer begins. When the time delay elapses the relay will automatically re-energize. There are no field adjustments or calibrations to the device. |
|