Product Description
Description: Phase Monitor Relays • Nominal AC Voltages: 575 VAC • Voltage Range: +5 to -15% • Frequency: 60Hz • Power Consumption (per phase): 2W • Contact Rating : DPDT 10 amps at 240VAC resistive • Mounting : Surface
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Nominal AC Voltages | 575 VAC |
Voltage Range | +5 to -15% |
Frequency | 60Hz |
Power Consumption (per phase) | 2W |
Transient Protection | 2500VRMS for 10ms |
Repeat Accuracy | ± 0.1% (fixed conditions) |
Unbalance Adjustment | 2% to 10% |
Response Time | 100ms |
Reset Time | Fixed 1 sec |
Dropout Time | Adjustable 0.2 to 20 seconds |
Reset Type | Automatic |
Dead Band | 0.5% max |
Contact Rating | DPDT 10 amps at 240VAC resistive |
Expected Relay Life | Mech: 10 million operations Elec: 100,000 operations at rated load |
Operating Temp | - 20° to +131° F |
Humidity Tolerance | 0-97% w/o condensation |
Mounting | Surface |
Enclosure Material | ABS plastic |
Weight | 10 oz. |
Series Features |
MODEL 200 3-Phase Voltage Unbalance Monitor |
Series Description: The Model 200 3-Phase Voltage Unbalance Monitor is designed to continuously monitor a three-phase line for unbalanced voltage conditions. This device will only energize the relay if an unbalance exists. Zero volts on all three phases is considered a balanced condition. This allows the Model 200 to be used with shunt breakers, so that the breaker can shut off the main power without tripping the monitor. The solid-state sensing circuit drives an internal electromechanical relay. Indicator lights on the monitor show when the voltage balance is within an acceptable range; when an unbalance exists; and when the relay is actually tripped. When an acceptable voltage balance is reapplied, the Model 200 will automatically reset the relay. |
|