Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Function | Phase Loss, Reversal, Low Voltage |
Nominal voltage | 480 VAC |
Adjustment Range | 380-480 |
Power Consumption | 6.7W |
Frequency | 60Hz |
Transient Protection | 2500V for 10ms |
Repeat Accuracy | ±0.1% (fixed conditions) |
Response Time | 0.05 seconds |
Reset Time | 0.05 seconds |
Reset Type | Automatic |
Dead Band | Approximately 2% |
Output Contacts | 10A@240VAC |
Expected Relay Life | Mech: 10 million operations Elec: 100,000 operations@rated load |
Operating Temperature | -20° to +131° F |
Humidity Tolerance | 0-97% w/o condensation |
Enclosure Material | ABS plastic |
Mounting | Surface |
Weight | 12 oz. |
Series Features |
MODEL 2638 3-Phase Monitor with Line Voltage & Phase Sequence Indicator |
Series Description: The Model 2638 3-Phase Monitor combines a 3-phase monitor with a line voltage and phase sequence indicator. Like other Time Mark Monitors, the Model 2638 senses phase loss, phase reversal and low voltage. When power and phasing are correct, the internal relay energizes. LED indicators will show that all phases are present, and the direction of phase rotation. When a fault occurs, the monitor trips its relay and indicates which phase is lost, or, if a reversal is present. This allows you to automatically protect your equipment by correcting the appropriate fault condition. The Model 2638 will automatically reset when correct power is restored. It is available in 208/240 VAC |
|