Product Description
Description: Phase Monitor Relays • Nominal voltage : 415 VAC • Trip Point: - • Power Consumption: - • Trip Point Tolerance: ± 2% • Frequency: 60Hz • Contact Rating : SPDT 10 amps at 240VAC resistive • Enclosure Material : ABS plastic
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Nominal voltage | 415 VAC |
Trip Point | - |
Power Consumption | - |
Trip Point Tolerance | ± 2% |
Frequency | 60Hz |
Transient Protection | 2500 VRMS for 10ms |
Repeat Accuracy | ±0.1% (fixed conditions) |
Response Time | 50ms (set or reset) |
Dead Band | Approx. 4% |
Contact Rating | SPDT 10 amps at 240VAC resistive |
Expected Relay Life | Mech:10 million operations Elec: 100,000 operations at rated load |
Operating Temperature | - 20o to +131o F |
Humidity Tolerance | 97% w/o condensation |
Enclosure Material | ABS plastic |
Agency Approvals | Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc. |
Series Features |
MODEL 2581 3-Phase Monitor |
Series Description: The Model 2581 3-Phase Monitor is designed to continuously monitor 3-phase power lines for phase loss, low voltage and phase reversal. The Model 2581 Monitor will detect phase loss on a loaded motor even when regenerated voltage is present. This device consists of a solid-state voltage and phase-angle sensing circuit, driving an electromechanical relay. When correct voltage and phase rotation are applied, the internal relay will energize. A fault condition will de-energize the relay. When the fault is corrected, the monitor will automatically reset . The Model 2581 3-Phase Monitor does not require a neutral connection and can be used with Wye or Delta configured systems. Low voltage trip point is factory set at 10% below nominal. An LED indicator is provided for system troubleshooting. |
|