Product Description
Description: Phase Monitor Relays • Operating Voltage: 95-120 VAC • Power Consumption: 6W at 120V • Auto Ranges: No • Reset: Manual • Frequency: 50/60Hz • Output Contacts : 2X SPDT 10A at 240VAC resistive • Mounting : Surface Mount
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Operating Voltage | 95-120 VAC |
Power Consumption | 6W at 120V |
Auto Ranges | No |
Reset | Manual |
Frequency | 50/60Hz |
Type of Measurement | RMS |
Under Voltage Trip Reset | (% of setpoint) 90% ±1% 93% ±1% |
Over Voltage Trip Reset | (% of setpoint) 110% ±1% 107% ±1% |
Voltage Unbalance Trip Reset | (conforms to NEMA) 2-8%, adjustable Trip setting minus 0.7% |
Trip Delay Time Over, Under, & Unbalanced Single-Phasing Faults Unbalance > 15% | 1-30 sec., adjustable 1 sec., fixed 1 sec., fixed |
Restart Delay | 1-500 sec., adjustable |
Manual Reset Input | 5V open circuit/500?A short circuit |
Output Contacts | 2X SPDT 10A at 240VAC resistive |
Operating Temp | - 20o to +140o F |
Humidity Tolerance | 0-97% w/o condensation |
Terminal Torque | 9 in lbs max for power and relay terminals 5.3 in lbs max for manual reset terminals |
Wire Type | 12 - 22 AWG for power and relay terminals 12 - 30 AWG for manual reset terminals |
Enclosure | Noryl plastic |
Mounting | Surface Mount |
Weight | 12.5 oz. |
Additional Options | /SG = Silver with Gold Flash Contacts |
Series Features |
MODEL 22 3-Phase Monitor with Adjustable Trip & Restart Delays |
Series Description: A microcontroller-based universal 3-phase monitor for protecting 3-phase motors from abnormal power conditions. It can detect under voltage, over voltage, voltage unbalance, reverse phase, and single-phasing even when regenerated voltage is present. The Model 22 includes adjustable trip and restart delays to prevent nuisance tripping during power fluctuations and short cycling in compressor applications. The LED status indicators and adjustment pots for Voltage Adjustment, % Unbalance, Restart Delay and Trip Delay are mounted on the front of the unit for easy access along with 2 SPDT relay contacts. Automatic or manual restart versions are available. The Model 22 does not require a neutral connection and can be used on either Wye or Delta systems. All versions of the Model 22 are available with optional gold flashed silver contacts for low current applications. |
|