| Manufacturer | TimeMark |
| Manufacturer Product Number | 19-380-50/SG |
| Description | Phase Monitor Relay; 3-Phase; 380V AC; 300...400V AC |
| Datasheet | Download Datasheet |
The TimeMark 19-380-50/SG is a 3-phase monitor for 380 V AC, 50 Hz systems. It drops its output relay out on phase loss, phase reversal and undervoltage and resets once the fault clears.
Trip points: undervoltage 300-400 V AC. Adjustment: field adjustable. Trip delay: undervoltage 1-30 s (adjustable). Restart: 1-300 s (adjustable). Reset: automatic.
Output: 1C SPDT (silver with gold flash), 5 A at 120 V AC resistive. Mounting: plug-in, on an 8-pin octal (TimeMark 51X120 socket) base. Indicator: "FAULT" (red) and "NORM" (green) condition indicators. Approvals: UL Recognized (U.S. and Canada). It operates from -29 to +55 °C.
| Category | |
| Manufacturer | TimeMark |
| Model | 19 |