Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 105-130VAC |
Input frequency | 47-65Hz |
Power consumption | 2W |
Air pressure input | 0-15 psi max. |
Input air supply fitting | Requires 3/16 I.D. tubing |
Maximum liquid level displayed | 34.6 feet |
Calibration accuracy | ± 2% |
Repeat accuracy (fixed condition) | ± 1% |
Repeat accuracy (0-60º C) | ± 2% |
Dead band | 0.1 foot |
Switching outputs | 4 open-collector transistors rated for regulated 12VDC, 10mA, maximum. Designed as inputs for the Model 403 Liquid Level Controller or Model 448 Output Relay Board |
Signal outputs | 4-20mA output proportional to 0-34.6 feet of water |
Operating temperature | - 20º to +122º F |
Storage temperature | - 4º to +158º F |
Humidity tolerance | 0-97% without condensation |
Case material | 20 gauge Steel |
Termination | Removable terminal strip |
Series Features |
MODEL 404 Liquid Level Sensor |
Series Description: The Model 404 Liquid Level Sensor operates in con- junction with a Model 403 Controller for bubbler-type du- plex pumping systems. The 404 contains an air pressure- to-voltage transducer and requires only a small compres- sor capable of 15 psi (pounds per square inch) to operate the system down to approximately 35 feet. The Model 404s four outputs are designed to replace the float switch inputs to a Model 403, or to be used with a Model 448 Output Relay Board. A 4-20mA signal output provides for other control applications. A 3-digit LED display continuously shows the liquid level to a tenth of a foot when the Display Control switch is in the Liquid Level position. Other settings of the switch al- low setting of the liquid level trip points. LED Indicators illuminate as the levels are exceeded. A test control allows the trip settings to be checked without actually raising or lowering the liquid level. |
|