Product Description
|
| Product Information | Resources |
|
| Specifications |
| Product Attribute | Attribute Value |
| Nominal Voltage | 120VAC ±10% |
| Frequency | 50/60 Hz |
| Power Consumption | 9W |
| Transient Protection | 2500 VRMS for 10ms |
| Switch Current | 5mA Max |
| Switch Voltage | 5VDC |
| Loop Output | adjustable 4 to 20mA no switches closed = 4mA output |
| Operating Environment | -4º to +122º F |
| Humidity Tolerance | 97% w/o condensation |
| Enclosure Material | ABS plastic |
| Series Features |
| MODEL 460D Switch-to-Loop Converter |
| Series Description: Liquid level controllers generally require a 4-20mA loop current. The loop current indicates the level of liquid in a tank or reservoir, and is usually generated by an expensive pressure transducer or ultrasonic sensor. If you already have a tank with float switches installed, the Model 460D Switch-to-Loop Converter allows you to take advantage of the latest liquid level control, without the added cost of a transducer. The Model 460D Converter outputs a specific current value as each of the six inputs are closed. Current values are individually adjustable between 4 and 20mA for each switch input. Up to six switches can be used as inputs to all liquid level devices accepting a 4-20mA input, such as Time MarkÕs Model 4052. |
|