Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 90-140VAC |
Power consumption | 2.5W |
Transient Protection | 2500VRMS for 10ms |
Probe voltage | (open circuit) 15 VRMS |
Probe current | 5mA maximum |
Sensitivity adjust | 1K ohms-100K ohms |
Contacts | DPDT |
Contact Rating | 7.5A @ 240 VAC resistive |
Expected relay life | Mechanical: 10 million operations Electrical: 100,000 oper. at rated load |
Response Time | 300ms |
Reset Time | <1 second |
Time delay accuracy | ±5% |
Operating Temp | - 20° to 60° C |
Humidity Tolerance | 0-97% w/o condensa |
Case Material | NORYL |
Mounting | 11-Pin Socket ( **sold separately) |
Series Features |
MODEL 409D Liquid Level Controller |
Series Description: The Model 409D is a compact, socket-mount device for level control of conductive liquids. The internal relay is energized when operating power is applied. When the liquid level reaches the probe, the relay de-energizes. When the level drops below the probe, the relay will reset. A fixed, 300ms time delay prevents oscillation due to wave action. Probe cables may be shielded or unshielded. If the liquid container is made of a non-conductive material, a common electrode is required. Other features include an LED indicator to show the output relay status and an adjustable sensitivity setting. Requires a standard 11-pin octal socket (such as the Time Mark model 51X016). |
|