Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 80-550 VAC |
Input Current | 1mA |
Frequency | 50/60Hz nominal |
DC Power | 24 Volts, 2 watts |
Output | 240V AC, 10A, Resistive 120V AC, 4A, General Use 240V AC, 2A, General Use C300, Pilot Duty |
Start-up Delay | 5 secs. Min. or Automatic reset delay setting (to allow for solid lock) |
Frequency Range | 40Hz to 70Hz 320Hz to 560Hz with 400Hz jumpe |
Output Contacts | SPDT x 2 10 Amps @ 240VAC |
Repeat Accuracy | ± 0.5 % (fixed conditions) |
Reset Type | Manual or Automatic |
Expected Relay Life | Mech: 10 million operations Elec: 100,000 min. at rated load |
Operating Temp | -20°F to +130°F |
Humidity Tolerance | 0-97% w/o condensation |
Enclosure | Material Lexan Polycarbonate |
Mounting | Din Rail 35mm |
Series Features |
MODEL 29 Frequency Monitor |
Series Description: Model 29 Frequency Monitor has a display that shows the frequency with an accuracy of +/- 0.5%. The display is updated every second and re-initialized every 30 seconds. Model 29 has a rotary encoder with switch on the unit. By pressing the encoder switch for more than 5 seconds, the unit will enter the setup mode. This unit has a user selectable relay option for High-Low or DPDT. It can also be user-selected to energize on fault or de-energize on fault. The user can select automatic or manual restart on the Model 29. The SG version of the Model 29 has silver with gold flash contacts for low current applications. Model 29 Frequency Monitor can be restored to factory defaults. |
|