Product Description
|
| Product Information | Resources |
|
| Specifications |
| Product Attribute | Attribute Value |
| Supply voltage | 115VAC @ 50/60Hz |
| Input current | 0-5 amps |
| Input frequencies | 25-400Hz |
| Input burden | 0.5VA at 120VAC 60Hz |
| Output @ rated input | 4-20 mA |
| Maximum load | 500 ohms |
| Output accuracy | 2% at 77°F |
| Output ripple | 1% max at nominal frequency |
| Response time | 800ms from 0-99% |
| Overload withstand | 2 times rated output-continuous 10 times rated input-1 second |
| Dielectric withstand voltage (isolation) | 1500 VRMS input, output, case |
| Operating temperature | -20° to +131°F |
| Humidity tolerance | 0-97% w/o condensation |
| Enclosure material | ABS plastic |
| Mounting | 8-pin socket (*order separately) |
| Agency Approvals | UL Recognized-US/Canada |
| Series Features |
| MODEL 278 AC Current Transducer |
| Series Description: The Model 278 AC Current Transducer is designed to accept an AC current input, and provide a proportional DC current output. A linear transformer input is coupled to a solid-state output amplifier. The Model 278 is powered by a 115VAC |
|