Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Supply voltage | 115VAC @ 50/60Hz |
Input current | 0-5 amps |
Input frequencies | 25-400Hz |
Input burden | 0.5VA at 120VAC 60Hz |
Output @ rated input | 4-20 mA |
Maximum load | 500 ohms |
Output accuracy | 2% at 77°F |
Output ripple | 1% max at nominal frequency |
Response time | 800ms from 0-99% |
Overload withstand | 2 times rated output-continuous 10 times rated input-1 second |
Dielectric withstand voltage (isolation) | 1500 VRMS input, output, case |
Operating temperature | -20° to +131°F |
Humidity tolerance | 0-97% w/o condensation |
Enclosure material | ABS plastic |
Mounting | 8-pin socket (*order separately) |
Agency Approvals | UL Recognized-US/Canada |
Series Features |
MODEL 278 AC Current Transducer |
Series Description: The Model 278 AC Current Transducer is designed to accept an AC current input, and provide a proportional DC current output. A linear transformer input is coupled to a solid-state output amplifier. The Model 278 is powered by a 115VAC |
|