Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | TimeMark |
| Manufacturer Product Number | 2780-115 |
| Description | Current Transducers; 0-5 A AC; 0-10 V DC; 115V AC, 50/60 Hz; Socketable |
| Datasheet | Download Datasheet |
The TimeMark 2780-115 is an AC current transducer that turns a 0-5 A AC current, normally the secondary of a current transformer, into a 0-10 V DC signal for a meter, PLC or controller. It runs from 115V AC, 50/60 Hz.
Input: 0-5 A AC, 25-400 Hz. Sensing: internal linear transformer; 0-5 A from an external CT (TimeMark 276). Accuracy: 2% at 25 °C. Response: 800 ms (0-99%). Isolation: 1500 VRMS input, output, case.
Mounting: plug-in, on an 8-pin octal base (TimeMark 51X120 socket, sold separately).
| Category | |
| Manufacturer | TimeMark |
| Model | 2780 |
| Sensor Type | Internal linear transformer; 0-5 A from an external CT (TimeMark 276) |
| Current Range | 0-5 A AC |
| Input Range | 0-5 A AC, 25-400 Hz |
| Output Signal | 0-10 V DC |
| Supply Voltage | 115V AC, 50/60 Hz |
| Accuracy | 2% at 25 °C |
| Response Time | 800 ms (0-99%) |
| Isolation | 1500 VRMS input, output, case |
| Mounting Type | Socketable |
| Termination Style | Plug In, 8 Pin (Octal) |