Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Function | AC Over Current / Under Current |
Supply Voltage | none required |
Input Current | Minimum: 25A Maximum: 150A |
Adjustment Range | 25 to 150A |
Maximum Wire Size | 2 AWG |
Response Time | 100ms |
Contact Rating | 10A@240VAC |
Repeat Accuracy | 1% max. |
Dead Band | Approximately 2% |
Operating Temperature | - 20° to +140° F |
Reset | Automatic |
Terminals | 1/4 quick connects |
Enclosure Material | ABS plastic |
Mounting | Surface Mount or DIN Rail 35mm |
Weight | 3.5 oz. |
Series Features |
MODEL 1732 AC Current Monitor |
Series Description: The Model 1732 AC Current Monitor is a single setpoint current monitor. It can be used to detect either over current or under current, depending on whether the trip point is set above or below the input current. Dual LED indicators on the front or top of the unit give a clear visual reference for a fault condition. The Model 1732 generates its operating voltage from the monitored current line, so no external power supply is required. A current greater than 25A is needed to energize the internal relay. The maximum current set point is 150A. The Model 1732 is not frequency sensitive, and can be used on AC currents from 50 to 400Hz. The compact housing can be surface or DIN rail mounted. |
|