| Manufacturer | TimeMark |
| Manufacturer Product Number | 295-240 |
| Description | Capacitor Trip Device; 240V AC (190 - 240V AC); 28.7 W-s at 240 V AC input |
| Datasheet | Download Datasheet |
The TimeMark 295-240 is a capacitor trip device for a 240V AC (190 - 240V AC) supply.
Output: 339 V DC. Stored energy: 28.7 W-s at 240 V AC input. Hold-up: 12 s or more after power loss. Trips by: manual, or by a control relay / phase-loss or power-fail monitor contact. For use with: shunt-trip circuit breakers. Indicators: low-energy lamp across the capacitor. Body: 20 gauge cold-rolled steel.
Mounting: surface mount. Dimensions: 2.58" wide; 7.0" overall height (6.25" / 5.53" inner dims, 1.25" top to hole, 1.44" bottom); depth views 3.25" / 2.80"; .37" dia mounting hole. It operates from -29 to +55 °C.
| Category | |
| Manufacturer | TimeMark |
| Model | 295 |
| Device Type | Line-charged capacitor trip device |
| Input Voltage | 240V AC (190 - 240V AC) |
| Output Voltage | 339 V DC |
| Stored Energy | 28.7 W-s at 240 V AC input |
| Hold-Up Time | 12 s or more after power loss |
| Trip Initiation | Manual, or by a control relay / phase-loss or power-fail monitor contact |
| For Use With | Shunt-trip circuit breakers |
| Status Indicator | Low-energy lamp across the capacitor |
| Mounting Type | Surface Mount |
| Housing Material | 20 gauge cold-rolled steel |
| Dimensions | 2.58" wide; 7.0" overall height (6.25" / 5.53" inner dims, 1.25" top to hole, 1.44" bottom); depth views 3.25" / 2.80"; .37" dia mounting hole |
| Operating Temperature (°C) | -29...+55 |