Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Nominal input voltage | 120VAC |
Input voltage range | 90-120VAC |
Output voltage | 170VDC |
Frequency range | 50 - 400Hz |
Operating temperature | -20º to +131º F |
Humidity tolerance | 0-97% w/o condensation |
Case material | 20 Gauge CRS |
Mounting | Surface Mount |
Weight | 2 lbs. |
Series Features |
MODEL 295 Capacitor Trip Device |
Series Description: The Model 295 Capacitor Trip Device is used to trip circuit breakers by using the stored energy in a capacitor. The capacitor is kept@full charge during normal operation by a half-wave silicon rectifier which draws its energy from the power line. When completely discharged, the Model 295 draws approximately 10A from the line in the first half cycle, 3A the second half cycle and 1 amp from the third. Continuous current required to keep the capacitor charged is less than 5 milliamps. The capacitor holds sufficient charge to trip the breaker for@least 12 seconds after the charging voltage is removed. However, on most fault conditions, some voltage is still present, so the Model 295 is designed so that 65% of normal voltage gives sufficient charge to trip the breaker. A low-energy lamp, connected in parallel with the storage capacitor, gives a visual indication when the voltage charge is 85 volts or more on the 120V version and 170 volts or more on the 240V version. |
|