Product Description
Description: Relays • Alternating Sequencing Relay • Input voltage : 120VAC +/- 10% 50/60Hz • Power Consumption : 6.0 watts max. • Output configuration : SPST • Mounting : Base Mount • Output Contact Rating : SPST 5A at 240VAC or 5A at 30VDC resistive
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input voltage | 120VAC +/- 10% 50/60Hz |
Power Consumption | 6.0 watts max. |
Output configuration | SPST |
Mounting | Base Mount |
Transient Protection | 2500 VRMS for 10ms |
Delay Between Relay Operations | 5 seconds |
Output Contact Rating | SPST 5A at 240VAC or 5A at 30VDC resistive |
Input Contact Requirement | 0.001 amp at 12VDC |
Expected Relay Life | Mech: 50 million operations Elec: 100,000 ops at rated load |
Operating Temperature | -20o to+140o F |
Humidity Tolerance | 0 - 97% w/o condensation |
Enclosure Material | ABS plastic |
Weight | 1.0 lbs. |
Series Features |
MODEL 441 Multi-Stage Alternator |
Series Description: The Model 441 Multi-Stage Alternator is designed to control the operating sequence of multi-stage motor/pumping systems. It can also be used to maintain the desired level of pressure-on air compressor systems. Four motor select DIP switches located on the front panel allow the alternator to control a single-motor/pump, two-motor/pump, three-motor/pump or four-motor/pump system. The Model 441 will assure that only the necessary motors/pumps are operating, and that the run time for each motor/pump is approximately equal. Motors are sequenced first-on, first-off. If the motor/pumping demand requires only one motor/pump at a time, the alternator will start the next motor/pump in sequence each time an input switch is closed. Input switches may be float switches, pressure switches, flow switches, etc. , as required by the application. Potential uses for the Model 441 include water supply systems, sewage disposal plant systems, storage tank filling systems, air compressor systems, irrigation and water recycling systems. |
|