Product Description
Description: Solid State Contactors • Input Voltage: 90-280VAC • Switching: SCR • Turn on: Random Turn On • Load Voltage: 480 VAC • Load Current: 75 Amp
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 90-280VAC |
Switching | SCR |
Turn on | Random Turn On |
Load Voltage | 480 VAC |
Load Current | 75 Amp |
Min. Load current to maintain on | 250mA |
Non-Repetitive Surge Current (1 cycle) | 1150A |
Maximum I2T for Fusing (Asquared sec) | 2600A2 S |
Suggested Heatsink °C/W | 0.14°C/W + Fan(2) |
Load Voltage Range | 50 to 480 VAC |
Frequency Range | 47 to 63 Hz |
Peak Blocking Voltage | 800 to 1200 |
Maximum Rate of Rise Off State Voltage (dv/dt) | 500V/uS |
Max. Off state leakage current (rms) | 10mA |
Max On State Voltage Drop | 1.8VAC |
Maximum Turn-On time @ 60 Hz | 8.3mS |
Maximum Turn-Off time @ 60 Hz | 8.3mS |
Dielectric Strength - I or O case | 400Vrms |
Temperature | Operating: - 30 to 80°C Storage: -40 to 100°C |
Series Features |
645S Series - Solid State On / Off Motor Relays |
Series Description: The 645S series of solid state relays uses back to back SCRs for on/control of three phase loads. Operation is three pole normally open. Inputs can be AC or DC operated. Load currents can range from 10 to 75 amps and up to a nominal voltage of 480VAC. Both random turn on or zero cross construction is available. |