Product Description
Description: Monitors • Voltage Monitor Relays • Input Voltage : 200 - 480 Vac • Restart Function; Lockout, min off time • Mounting ; Surface Mount • Contact Configuration; SPDT & NO • Termination Type; Screw terminal with captive wire clamps for up to #14 AWG (2.5 mm²) wire • Voltage Unbalance; Adjustable 2-10% • Trip Delay; Adjustable 1-30s • Restart Delay; Adjustable 0.6-300s
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 200 - 480 Vac |
Restart Function | Lockout, min off time |
Mounting | Surface Mount |
Contact Configuration | SPDT & NO |
Termination Type | Screw terminal with captive wire clamps for up to #14 AWG (2.5 mm²) wire |
Voltage Unbalance | Adjustable 2-10% |
Trip Delay | Adjustable 1-30s |
Restart Delay | Adjustable 0.6-300s |
Series Features |
Voltage Monitors |
Series Description: The DLMU Series is a universal voltage, 3-phase voltage monitor. It continuously measures the voltage of each of the three phases with microcontroller accuracy and compares the value to preset trip points. It separately senses phase reversal and loss; over, under and unbalanced voltages; and over or under frequency. Protection is assured during periods of large average voltage fluctuations or when regenerated voltages are present. The unit trips within 200ms when phase loss is detected. Adjustable time delays are included to prevent nuisance tripping and short cycling of sensitive equipment. The isolated, 10A, SPDT and 2A alarm output relay contacts trip when a phase voltage exceeds the trip limits for the trip delay. Nominal line voltage, voltage unbalance, and time delays are knob adjustable. The phase loss setpoint and the acceptable frequency range are fixed. Both delta and wye systems can be monitored; no connection to neutral is required |
Operation: Upon application of line voltage, the output is de-energized and the restart delay begins. If all the 3-phase voltages are within the acceptable range, the output energizes at the end of the restart delay. The microcontroller circuitry automatically senses the voltage range, and selects the correct operating frequency (50 or 60Hz). The over and undervoltage trip points are set automatically. When the measured value of any phase voltage exceeds the acceptable range limits (lower or upper) the trip delay begins. At the end of the trip delay the output relay de-energizes. If the phase voltage returns to an acceptable value before the trip delay expires, the trip delay is reset and the output remains energized. Under, over, and unbalanced voltages plus over or under frequency must be sensed for the complete trip delay before the unit trips. The unit trips in 200ms when phase loss or reversal are sensed. The unit will not energize if a fault is sensed as the line voltage is applied. Reset: Reset is automatic upon correction of the voltage or frequency fault or phase sequence.r |
|