Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | SSAC / Littelfuse |
| Manufacturer Product Number | KRD94110SA |
| Description | TDR; 10 s; Fixed; 120V AC; Output initially de-energized; 1C SPDT |
| Datasheet | Download Datasheet |
The Littelfuse SSAC KRD94110SA is a retriggerable single shot timer for 120 V AC, with isolated SPDT relay contacts rated 10 A resistive at 125 V AC. Its delay is fixed at 10 seconds, set at the factory.
Input voltage must be applied before and during timing. Closing the initiate switch energizes the output and starts the delay; at the end of it the output de-energizes. Reclosing the switch resets the delay and restarts timing with the output still energized (retriggerable).
Output: 1C SPDT relay, 10 A resistive at 125 V AC; 5 A resistive at 230 V AC and 28 V DC; 1/4 hp at 125 V AC (at 40 °C), output initially de-energized. Repeat accuracy: ±0.5% or 20 ms, whichever is greater. Setting accuracy: Factory calibration ±5%; ±5% over temperature and voltage. Reset time: 150 ms. Supply tolerance: -20% / +10% of nominal; 50/60 Hz. Power: 2 VA. Life: 10,000,000 operations mechanical, 100,000 electrical.
It is surface mounted and has 0.250 in (6.3 mm) male quick-connect terminals. It operates from -20 to +60 °C and stores from -40 to +85 °C.
| Category | |
| Manufacturer | SSAC / Littelfuse |
| Model | KRD9 |
| Output Technology | Electromechanical Relay |
| Timing Function | Retriggerable Single Shot |
| Delay Time | 10 s |
| Timing Adjustment Method | Fixed, factory set |
| Options | Output initially de-energized |
| Timing Initiate Method | Control Switch |
| Contact Configuration | 1C SPDT |
| Output Rating | 10 A resistive at 125 V AC; 5 A resistive at 230 V AC and 28 V DC; 1/4 hp at 125 V AC (at 40 °C) |
| Input Voltage | 120V AC |
| Termination Style | Quick Connect - 0.250" (6.3mm) |
| Mounting Type | Surface Mount |
| Operating Temperature | -20...+60 °C (-40...+85 °C) |
| Setting Accuracy (%) | Factory calibration ±5%; ±5% over temperature and voltage |
| Repeatability (%) | ±0.5% or 20 ms, whichever is greater |
| Recovery Time (ms) | 150 |
| Mechanical Life | 10,000,000 cycles (100,000 cycles) |
| Input Operating Range | -20% / +10% of nominal; 50/60 Hz |
| Rated Power | 2 VA |