Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Mersen / Ferraz Shawmut |
| Manufacturer Product Number | STZ208Y20BXT |
| Description | Surge Protection Device; 208/120 V AC; 208/120 V 3-Phase Wye |
| Datasheet | Download Datasheet |
The Mersen / Ferraz Shawmut STZ208Y20BXT is a UL Type 1 surge protection device for 208/120 V AC 208/120 v 3-phase wye systems: enclosed unit for external mounting.
A UL Type 1 SPD is permanently connected and may be installed on the line side of the service disconnect as well as the load side.
Maximum continuous operating voltage (MCOV / Uc): L-N 150 V, L-G 150 V, L-L 239 V, N-G 150 V. Voltage protection rating (UL VPR): L-N 800 V, L-G 900 V, L-L 1200 V, N-G 800 V (with integral switch). Nominal discharge current (In): 20 kA (8x20 µs). Maximum discharge current (Imax): 200 kA. Short circuit current rating (SCCR): 200 kA. Modes of protection: L-N, L-G, L-L, N-G, for 50 Hz or 60 Hz networks.
Status indication: lED status indicator: green = 67 to 100% life, yellow = 34 to 66% life, red = 0 to 33% life; LED phase loss indication. Up to -50 dB from 10 kHz to 100 MHz. Monitoring: audible alarm with silence button; phase loss indication; surge counter. Back-up fuse: Not required (does not require additional overcurrent protection). Response time Less than 1 nanosecond (one per phase).
Mounting: externally mounted panel. Connection: 8 AWG - 1/0 phase and neutral; 8 AWG - 2/0 ground (see installation instructions for details by option and lug torque). Protection: NEMA 4X. Housing: stainless steel; UL94-5VA. It operates from -35 °C to +85 °C (-31 °F to +185 °F), operating and storage °C. Size: 12.61 in (320.3 mm) W x 16.28 in (413.6 mm) H, 17.50 in (444.5 mm) H with mounting flanges, 6.29 in (159.8 mm) D enclosure, 8.06 in (204.8 mm) D including switch handle; mounting holes 4x dia. 0.31 in (7.9 mm), 10.00 in (254 mm) apart.
Approvals: UL Listed, CSA Certified, RoHS.
| Category | |
| Manufacturer | Mersen / Ferraz Shawmut |
| Model | STZ |
| SPD Type | UL 1449 Type 1 (panel mount SPD for UL 1449 Type 1 and 2 applications) |
| Product Form | Enclosed unit for external mounting |
| Configuration | 208/120 V 3-Phase Wye |
| Nominal System Voltage | 208/120 V AC |
| Max Continuous Operating Voltage | L-N 150 V, L-G 150 V, L-L 239 V, N-G 150 V |
| Voltage Protection Rating | L-N 800 V, L-G 900 V, L-L 1200 V, N-G 800 V (with integral switch) |
| Nominal Discharge Current | 20 kA (8x20 µs) |
| Maximum Discharge Current | 200 kA |
| Short Circuit Current Rating | 200 kA |
| Modes of Protection | L-N, L-G, L-L, N-G |
| Network Systems | 50 Hz or 60 Hz |
| Status Indication | LED status indicator: green = 67 to 100% life, yellow = 34 to 66% life, red = 0 to 33% life; LED phase loss indication |
| Remote Contact | Form C dry contacts |
| Thermal Protection | Yes (Mersen TPMOV technology) |
| EMI/RFI Filtering | Up to -50 dB from 10 kHz to 100 MHz |
| Alarms / Monitoring | Audible alarm with silence button; phase loss indication; surge counter |
| Back-up Fuse | Not required (does not require additional overcurrent protection) |
| Response Time | Less than 1 nanosecond (one per phase) |
| Connection | 8 AWG - 1/0 phase and neutral; 8 AWG - 2/0 ground (see installation instructions for details by option and lug torque) |
| Mounting | Externally mounted panel |
| Degree of Protection | NEMA 4X |
| Housing Material | Stainless steel; UL94-5VA |
| Operating Temperature (°C) | -35 °C to +85 °C (-31 °F to +185 °F), operating and storage |
| Dimensions | 12.61 in (320.3 mm) W x 16.28 in (413.6 mm) H, 17.50 in (444.5 mm) H with mounting flanges, 6.29 in (159.8 mm) D enclosure, 8.06 in (204.8 mm) D including switch handle; mounting holes 4x dia. 0.31 in (7.9 mm), 10.00 in (254 mm) apart |
| Approvals | UL Listed, CSA Certified, RoHS |
| Features | Disconnect: UL 98 switch with door-mounted handle |