| Manufacturer | Mersen / Ferraz Shawmut |
| Manufacturer Product Number | STXT240H10 |
| Description | Surge Protection Device; 240/120 V AC; 3-phase high-leg delta |
| Datasheet | Download Datasheet |
The Mersen / Ferraz Shawmut STXT240H10 is a UL Type 1 surge protection device for 240/120 V AC 3-phase high-leg delta systems: panel-mount enclosed unit.
A UL Type 1 SPD is permanently connected and may be installed on the line side of the service disconnect as well as the load side.
Maximum continuous operating voltage (MCOV / Uc): L-N 150/275 V AC; L-G 150/275 V AC; N-G 150 V AC; L-L 300/425 V AC (L/HL values). Voltage protection rating (UL VPR): L-N 700/1200 V AC; L-G 700/1200 V AC; N-G 700 V AC; L-L 1000/2000 V AC (L/HL values). Nominal discharge current (In): 20 kA. Maximum discharge current (Imax): 100 kA per phase. Short circuit current rating (SCCR): 200 kA. Modes of protection: L-N, L-G, N-G, L-L, for 50 Hz or 60 Hz networks.
Status indication: lED per phase: green = functional, out = replace. Up to -50 dB from 10 kHz to 100 MHz. Monitoring: lED phase-loss indication. Response time Less than 1 ns (one per phase).
Mounting: female 3/4 in-14 threaded hub; mounting feet with 0.25 in diameter holes. Connection: Wire lugs for 8 AWG copper. Protection: NEMA 4X non-metallic enclosure. Housing: uL94-5VA. It operates from -40 to +85 °C (-40 to +185 °F), operating and storage; humidity 0 to 95% non-condensing °C. Size: 7.08 in W x 7.40 in H (incl. mounting feet) x 3.68 in D; 4 x 0.30 in dia. mounting holes on 3.50 x 6.70 in; 3/4 NPSM hub.
Approvals: UL Listed; CSA; RoHS.
| Category | |
| Manufacturer | Mersen / Ferraz Shawmut |
| Model | STXT |
| SPD Type | UL 1449 5th Edition Type 1 SPD; for Type 1 and Type 2 applications |
| Product Form | Panel-mount enclosed unit |
| Configuration | 3-phase high-leg delta |
| Nominal System Voltage | 240/120 V AC |
| Max Continuous Operating Voltage | L-N 150/275 V AC; L-G 150/275 V AC; N-G 150 V AC; L-L 300/425 V AC (L/HL values) |
| Voltage Protection Rating | L-N 700/1200 V AC; L-G 700/1200 V AC; N-G 700 V AC; L-L 1000/2000 V AC (L/HL values) |
| Nominal Discharge Current | 20 kA |
| Maximum Discharge Current | 100 kA per phase |
| Short Circuit Current Rating | 200 kA |
| Modes of Protection | L-N, L-G, N-G, L-L |
| Network Systems | 50 Hz or 60 Hz |
| Status Indication | LED per phase: green = functional, out = replace |
| Thermal Protection | Yes (TPMOV; no additional overcurrent protection needed) |
| EMI/RFI Filtering | Up to -50 dB from 10 kHz to 100 MHz |
| Alarms / Monitoring | LED phase-loss indication |
| Response Time | Less than 1 ns (one per phase) |
| Connection | Wire lugs for 8 AWG copper |
| Mounting | Female 3/4 in-14 threaded hub; mounting feet with 0.25 in diameter holes |
| Degree of Protection | NEMA 4X non-metallic enclosure |
| Housing Material | UL94-5VA |
| Operating Temperature (°C) | -40 to +85 °C (-40 to +185 °F), operating and storage; humidity 0 to 95% non-condensing |
| Dimensions | 7.08 in W x 7.40 in H (incl. mounting feet) x 3.68 in D; 4 x 0.30 in dia. mounting holes on 3.50 x 6.70 in; 3/4 NPSM hub |
| Approvals | UL Listed; CSA; RoHS |