Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Mersen / Ferraz Shawmut |
| Manufacturer Product Number | ST480SPG |
| Description | Surge Protection Device; 240/480 V AC; Split phase, 3-wire |
| Datasheet | Download Datasheet |
The Mersen / Ferraz Shawmut ST480SPG is a UL Type 1 surge protection device for 240/480 V AC split phase, 3-wire systems: monobloc DIN-rail unit.
A UL Type 1 SPD is permanently connected and may be installed on the line side of the service disconnect as well as the load side.
Maximum continuous operating voltage (MCOV / Uc): L-N 270 V AC; L-G 270 V AC; L-L 540 V AC. Voltage protection rating (UL VPR): L-N 800 V AC; L-G 800 V AC; L-L 1500 V AC. Nominal discharge current (In): 20 kA. Maximum discharge current (Imax): 50 kA. Short circuit current rating (SCCR): 200 kA. Modes of protection: L-N, L-G, L-L, for 50 Hz or 60 Hz networks.
Status indication: visual tab: tab out = replace. Monitoring: remote contact Signal wire #16-#30 AWG (1.5-0.05 mm2); torque 2.2 lb-in (0.25 Nm); 125 V AC 3 A; Comm-NO closed = product offline, not protected; Comm-NC closed = product online, protected; order the M version for Form C dry contacts. Response time Less than 1 ns (one per phase).
Mounting: 35 mm DIN rail. Connection: 6-14 AWG (25-2.5 mm2) solid / stranded Cu, torque 14.75 lb-in (1.67 Nm). Protection: IP20 (finger-safe). Housing: uL94 V0. It operates from -40 to +85 °C (-40 to +185 °F), operating and storage °C. Size: Width 1.39 in (35.5 mm); height 3.58 in (91.0 mm) body, 4.09 in (103.9 mm) overall; depth 2.70 in (68.5 mm).
Approvals: cURus (Type 1 Component Assembly); RoHS.
| Category | |
| Manufacturer | Mersen / Ferraz Shawmut |
| Model | ST |
| SPD Type | UL 1449 5th Edition Type 1 Component Assembly; for Type 1 and Type 2 applications |
| Product Form | Monobloc DIN-rail unit |
| Configuration | Split phase, 3-wire |
| Number of Poles | 2 poles |
| Nominal System Voltage | 240/480 V AC |
| Max Continuous Operating Voltage | L-N 270 V AC; L-G 270 V AC; L-L 540 V AC |
| Voltage Protection Rating | L-N 800 V AC; L-G 800 V AC; L-L 1500 V AC |
| Nominal Discharge Current | 20 kA |
| Maximum Discharge Current | 50 kA |
| Short Circuit Current Rating | 200 kA |
| Modes of Protection | L-N, L-G, L-L |
| Network Systems | 50 Hz or 60 Hz |
| Status Indication | Visual tab: tab out = replace |
| Thermal Protection | Yes (TPMOV, fail-safe self-protected; no additional overcurrent protection needed) |
| Alarms / Monitoring | Remote contact Signal wire #16-#30 AWG (1.5-0.05 mm2); torque 2.2 lb-in (0.25 Nm); 125 V AC 3 A; Comm-NO closed = product offline, not protected; Comm-NC closed = product online, protected; order the M version for Form C dry contacts |
| Response Time | Less than 1 ns (one per phase) |
| Connection | 6-14 AWG (25-2.5 mm2) solid / stranded Cu |
| Terminal Torque | 14.75 lb-in (1.67 Nm) |
| Mounting | 35 mm DIN rail |
| Degree of Protection | IP20 (finger-safe) |
| Housing Material | UL94 V0 |
| Operating Temperature (°C) | -40 to +85 °C (-40 to +185 °F), operating and storage |
| Dimensions | Width 1.39 in (35.5 mm); height 3.58 in (91.0 mm) body, 4.09 in (103.9 mm) overall; depth 2.70 in (68.5 mm) |
| Approvals | cURus (Type 1 Component Assembly); RoHS |