| Manufacturer | Mersen / Ferraz Shawmut |
| Manufacturer Product Number | M400U12 |
| Description | Disconnect Switch; 400 A; 3-pole; Non-fused |
| Datasheet | Download Datasheet |
The Mersen / Ferraz Shawmut M400U12 is a disconnect switch, supplied with a load-break: yes (fully rated load-break and load-make).
| Category | |
| Manufacturer | Mersen / Ferraz Shawmut |
| Model | UL 98 Non-Fusible |
| Switch Type | Non-fused |
| Current Rating | 400 A |
| Number of Poles | 3-pole |
| Handle Type | 1 pole left of handle, 2 poles right of handle |
| Rated Voltage | 600 V AC; DC 400 A at 250 V DC, 200 A at 600 V DC; 50 HP at 600 V DC (4-pole); 40 HP at 125 V DC in open air, 50 HP at 250 V DC in enclosure (2-pole); DC short circuit rating 10 kA with circuit breaker (4-pole); 14 kA at 250 V DC and 10 kA at 600 V D |
| Motor Rating | 125 HP (312.0 A FLA) at 240 V 3-phase; 250 HP (302.0 A FLA) at 480 V 3-phase; 350 HP (338.0 A FLA) at 600 V 3-phase |
| Short Circuit Rating | 100 kA with 600 A max. Class J fuses |
| Wire Size | 2-600 MCM |
| Tightening Torque | 375 lb-in; lug mounting 240 lb-in |
| Operating Temperature (°C) | -5 to 40 °C (general purpose amp rating); derate above 40 °C; Thermal current (Ith) multiplier by ambient: 35-40 °C 1.00; 40-45 °C 0.96; 45-50 °C 0.93; 50-55 °C 0.89; 55-60 °C 0.85; 60-65 °C 0.80; 65-70 °C 0.76; 70-75 °C 0.71; 75-80 °C 0.65; 80-85 °C |
| Approvals | cULus Listed, CSA, CE |
| Accessories | Direct handle HD400 (locking); external handles Pistol style HB125, HB145, HB274 (NEMA Type 1, 3R, 12); HB125X, HB145X, HB274X (NEMA Type 4, 4X); HM125X, HM175X (NEMA 4X stainless steel); substitute R for B for a red handle; ALRX10 alignment ring (op |
| Electrical Life | 1,000 operations |
| Mechanical Life | 16,000 operations |
| Features | Load-break: Yes (fully rated load-break and load-make) |
| IEC Ratings | Ie 400 A (AC-23A, up to 690 V); Ui 1000 V (IEC, AC20/DC20, pollution degree 3); Uimp 12 kV; dielectric 10 kV (50 Hz, 1 min); power loss per pole 10 W |
| Weight (lb) | 0.1 |