| Manufacturer | Macromatic |
| Manufacturer Product Number | TR-50628-22 |
| Description | Time Delay Relay; 0.1...10 min; True Off Delay; 24V AC/DC; 2C DPDT |
| Datasheet | Download Datasheet |
The Macromatic TR-50628-22 is a time delay relay with 2C DPDT output and rated 10 A at 240 V AC, 8 A at 28 V DC, driven by a 24V AC/DC input.
It is adjustable from 0.1 to 10 min and set by an onboard knob.
It is a True Off Delay timer.
Upon application of control voltage, the relay is energized. When the control voltage is removed, the preset time begins. At the end of the preset time, the relay is de-energized. Voltage must be applied for a minimum of 0.1 seconds to assure proper operation. Any application of the control voltage during the preset time will keep the relay energized & reset the time delay. No external trigger switch is required.
It is started by removing the supply.
It has Socketable mounting and Plug In terminals.
| Category | |
| Manufacturer | Macromatic |
| Model | TR-5 |
| Output Technology | Electromechanical Relay |
| Timing Function | True Off Delay |
| Delay Time | 0.1...10 min |
| Timing Adjustment Method | Onboard knob |
| Timing Initiate Method | Removal of Input Voltage |
| Contact Configuration | 2C DPDT |
| Output Rating | 10 A at 240 V AC, 8 A at 28 V DC |
| Pilot Duty | B300 & R300 |
| Input Voltage | 24V AC/DC |
| Termination Style | Plug In |
| Mounting Type | Socketable |
| Socket Family | 8 Pin Octal |
| Required Socket | 70169-D |
| Operating Temperature | -28...+65 °C (-40...+85 °C) |
| Approvals | UL (E109466), CSA Certified (LR45565), CE |
| Setting Accuracy (%) | Maximum setting +5%/-0%, minimum setting +0%/-50% |
| Repeatability (%) | +0.1% or +0.04 s, whichever is greater, at constant voltage and temperature |
| Start-Up Time | 0.05 s |
| Maintain Function Time | 0.01 s |
| Mechanical Life | 2,000,000 cycles (100,000 cycles) |
| Input Operating Range | +10%/-15% of nominal, AC at 50/60 Hz and DC |
| Rated Power | 2 VA |