Product Description
Description: Time Delay Relay • Delay on Make • Input Voltage: 24-240V AC & 12-48V DC • Timing Range: 1 - 100 Sec. • Mounting : Panel Mount • Contact Configuration: NO • Output Current: 1 Amp
| Product Information | Resources |
|
|
| Specifications |
| Product Attribute | Attribute Value |
| Input Voltage | 24-240V AC & 12-48V DC |
| Timing Range | 1 - 100 Sec. |
| Mounting | Panel Mount |
| Contact Configuration | NO |
| Output Current | 1 Amp |
| Voltage Tolerance | AC Operation: +10 to -15% of nominal voltage, 50/60 Hz DC Operation: +10 to -15% of nominal voltage |
| Load (Burden) | Maximum of 1 VA for all voltages |
| Setting Accuracy | Maximum Setting (Adjustable): +5%, -0% Minimum Setting (Adjustable): +0%, -50% Fixed Time Delay: +2% or 50ms, whichever is greater |
| Repeat Accuracy (constant voltage and temperature) | +0.1% or + 0.01 seconds, whichever is greater |
| Reset Time | 50ms |
| Start-up Time | (Time from when power is applied until unit is timing) 0.02 Seconds |
| Maintain Function Time | (Time unit continues to operate after power is removed) 0.01 Seconds |
| Temperature | Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF) |
| Output Contacts | Normally Open Solid State 1A Continuous, 10A Inrush @ 65o C, Pilot Duty |
| Life | No predictable failure if used within operating parameters. |
| Leakage Current (OFF-State) | < 5ma @ 240V AC |
| Minimum Load Current | 20ma |
| Effective Voltage Drop (ON-State) | Maximum 3V @ 1A for all voltages |
| Mounting | Surface with one #8 or #10 screw and a maximum tightening torque of 15 in-lbs |
| Termination | 0.25” male quick-connect terminals |
| Series Features |
| THL-1 Series Solid State Output Inline (Series-Connection) |
| Series Description: The cost effective design and compact size of the THL Series make them the ideal choice for many industrial & commercial applications. They utilize a microprocessor-based design for greater performance & maximum flexibility. These products have a two-terminal, series-connection with the load. A Normally Open output rated 1A continuous & 10A inrush is perfect for high duty cycle/long life applications. All products are encapsulated for protection in harsh environments. Choose between adjustable or fixed time delays, either onboard or remote. |
|
RoHS Compliant