AC Operation: +10 to -15% of nominal voltage, 50/60 Hz DC Operation: +10 to -15% of nominal voltage
Load (Burden)
Maximum of 1 VA for all voltages
Setting Accuracy
Maximum Setting (Adjustable): +5%, -0%
Minimum Setting (Adjustable): +0%, -50%
Fixed Time Delay: +2% or 50ms, whichever is greater
Repeat Accuracy (constant voltage and temperature)
+0.1% or + 0.01 seconds, whichever is greater
Reset Time
50ms
Start-up Time
(Time from when power is applied until unit is timing) 0.02 Seconds
Maintain Function Time
(Time unit continues to operate after power is removed) 0.01 Seconds
Temperature
Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF)
Output Contacts
Normally Open Solid State 1A Continuous, 10A Inrush @ 65o C, Pilot Duty
Life
No predictable failure if used within operating parameters.
Leakage Current (OFF-State)
< 5ma @ 240V AC
Minimum Load Current
20ma
Effective Voltage Drop (ON-State)
Maximum 3V @ 1A for all voltages
Mounting
Surface with one #8 or #10 screw and a maximum tightening torque of 15 in-lbs
Termination
0.25” male quick-connect terminals
Series Features
THL-1 Series Solid State Output Inline (Series-Connection)
Series Description:The cost effective design and compact size of the THL Series make them the ideal choice for many industrial & commercial applications. They utilize a microprocessor-based design for greater performance & maximum flexibility. These products have a two-terminal, series-connection with the load. A Normally Open output rated 1A continuous & 10A inrush is perfect for high duty cycle/long life applications. All products are encapsulated for protection in harsh environments. Choose between adjustable or fixed time delays, either onboard or remote.
Universal input voltage: 24-240V AC & 12-48V DC
Onboard & remote adjustable or fixed time delays from 0.01 seconds to 100 hours
Two-terminal series-connection with the load
Cost effective design & compact 2” x 2” enclosure are ideal for volume OEM applications
Microprocessor-based design for greater performance & maximum flexibility
Encapsulated for protection against harsh environments
Output rated 1A continuous/10A inrush pilot duty is perfect for high duty cycle/long life applications