Product Description
| 
 | 
| Product Information | Resources | 
| 
 | 
 | 
| Specifications | 
| Product Attribute | Attribute Value | 
| Input Voltage | 120V AC/DC | 
| Timing Range | 1 - 1,023 Sec. | 
| Mounting | Plug-in 8 Pin Octal | 
| Contact Configuration | 2C DPDT | 
| Output Current | 10 Amps | 
| Timing Adjustment | Digital | 
| Voltage Tolerance | AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal. | 
| Load (Burden) | 2 VA | 
| Setting Accuracy | Constant Voltage & Temperature w/i specifications: +0.1% of set time or +50ms, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +50ms, whichever is greater | 
| Repeat Accuracy | Constant Voltage & Temperature w/i specifications: +0.1% of set time or +0.02 seconds, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +0.02 seconds, whichever is greater +1% of set time or +0.02 seconds, whichever is greater | 
| Reset Time: | All Functions Triggered by a Control Switch: 0.04 Seconds All Other Functions: 0.1 Seconds | 
| Start-up Time: | (Time from when power is applied until unit is timing) 0.05 Seconds for all units | 
| Maintain Function Time: | (Time unit continues to operate after power is removed) 0.01 Seconds for all units | 
| Insulation Voltage: | 2,000 volts | 
| Temperature | Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF) | 
| Output Contacts | DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120V AC (N.C.) B300 & R300; AC15 & DC13 | 
| Life | Mechanical: 10,000,000 operations Full Load: 100,000 operations | 
| Compatibility | Using a solid state switch to initiate the time sequence is acceptable. | 
| Series Features | 
| TD-8 Series PROGRAMMABLE | SINGLE FUNCTION, DIP-Switch | Digital-Set | | 
| Series Description: The TD-8 Series time delay relays offer an easy and accurate method to select any time delay between 100ms and 1,023 hours. Programming is accomplished through the use of a 10-position DIP-switch. Each position is marked with a binary time increment. The required delay is selected by moving the switch of each increment to the ON position and adding their corresponding values (see examples below). This method provides a greater setting accuracy than is found on other units with an analog potentiometer. An LED indicates relay status. | 
| 
 | 
 
             
                         
             
   RoHS Compliant