Product Description
| 
 | 
| Product Information | Resources | 
| 
 | 
 | 
| Specifications | 
| Product Attribute | Attribute Value | 
| Input Voltage | 12V DC | 
| Timing Range | 0.05 Sec. - 999 Hr. | 
| Mounting | Plug-in 11 Pin Round | 
| Contact Configuration | 2C DPDT | 
| Output Current | 10 Amps | 
| LED | Red LED. Refer to instruction sheet provided with product to determine code for relay & timing status. | 
| Function | Triggered On Delay | 
| Timing Adjustment | Analog | 
| Insulation Voltage | 2,000 volts | 
| Life | Mechanical: 10,000,000 operations • Full Load: 100,000 operations | 
| Load (Burden) | 3 VA | 
| Maintain Function Time | (Time unit continues to time after power is removed) 0.01 Seconds for all units | 
| Output Contacts | DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),1/3HP @ 120/240V AC (N.C.), B300 & R300 | 
| Repeat Accuracy (constant voltage and temperature) | Constant Voltage & Temperature w/i specifications: +0.1% of set time or +0.02 seconds, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +0.02 seconds, whichever is greater | 
| Reset Time | On Delay/Interval/Flasher: 0.1 Seconds • Off Delay/Single Shot: 0.04 Seconds | 
| Setting Accuracy | Constant Voltage & Temperature w/i specifications: +0.1% of set time or +50ms, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +50ms, whichever is greater | 
| Start-up Time | (Time from when power is applied until unit is timing) 0.05 Seconds for all units | 
| Temperature | Operating: -28o to 65oC (-18o to 149oF); Storage: -40o to 85oC (-40o to 185oF) | 
| Initiating Units with Control Switch Triggers: | Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds. | 
| Voltage Tolerance | AC Operation: +10/-15% of nominal at 50/60 Hz., DC Operation: +10/-15% of nominal. | 
| Series Features | 
| TD-7 Series Time Ranger™ PROGRAMMABLE | MULTI-RANGE | Digital-Set | 
| Series Description: The TD-7 series of time delay relays offer an easy and accurate way to select any time delay between 50ms and 999 hours. Programming is accomplished by using a pushbutton thumbwheel to select one of seven built-in time ranges and three pushbutton thumbwheels to digitally set the time delay required. This method provides a greater setting accuracy than is found on other units with an analog potentiometer. An LED indicates timing mode and time out condition. Multi-function versions available. | 
| 
 | 
 
             
                         
             
   RoHS Compliant
  RoHS Compliant