Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Macromatic |
| Manufacturer Product Number | TR-6152U |
| Description | Time Delay Relay; 0.05 s...100 h; Single Shot; 24-240V AC & 12-125V DC |
| Datasheet | Download Datasheet |
The Macromatic TR-6152U is a time delay relay with 2C DPDT output and rated 10 A at 240 V AC, 10 A at 30 V DC, driven by a 24-240V AC & 12-125V DC input.
It is adjustable from 0.05 s to 100 h, over sixteen selectable scales and set by a rotary range switch and knob.
It is a Single Shot timer.
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized and the time delay (t) begins. During the time delay (t), the trigger is ignored. At the end of the time delay (t), the output is de-energized and the time delay relay is ready to accept another trigger.
It is started by a control switch.
It has Socketable mounting and Plug In terminals.
| Category | |
| Manufacturer | Macromatic |
| Model | TR-6 |
| Output Technology | Electromechanical Relay |
| Timing Function | Single Shot |
| Delay Time | 0.05 s...100 h |
| Time Ranges | A 0.05-0.5 s, B 0.1-1 s, C 0.5-5 s, D 1-10 s, E 3-30 s, F 6-60 s, G 0.2-2 min, H 0.5-5 min, I 1-10 min, J 3-30 min, K 6-60 min, L 0.2-2 h, M 0.5-5 h, N 1-10 h, O 2.4-24 h, P 10-100 h |
| Timing Adjustment Method | Rotary range switch and knob |
| Timing Initiate Method | Control Switch |
| Contact Configuration | 2C DPDT |
| Output Rating | 10 A at 240 V AC, 10 A at 30 V DC |
| Pilot Duty | B300 & R300; AC15 & DC13 |
| Input Voltage | 24-240V AC & 12-125V DC |
| Termination Style | Plug In |
| Mounting Type | Socketable |
| Socket Family | 11 Pin Octal |
| Required Socket | 70170-D |
| Operating Temperature | -28...+65 °C (-40...+85 °C) |
| Approvals | UL Recognized (E109466), CE |
| Setting Accuracy (%) | Maximum setting +5%/-0%, minimum setting +0%/-50% |
| Repeatability (%) | +0.1% or +50 ms, whichever is greater, at constant voltage and temperature |
| Start-Up Time | 0.05 s |
| Maintain Function Time | 0.01 s |
| Mechanical Life | 10,000,000 cycles (100,000 cycles) |
| Input Operating Range | 20.4...264 V AC at 50/60 Hz, 10.2...137.5 V DC |
| Rated Power | 3 VA |