| Manufacturer | Macromatic |
| Manufacturer Product Number | TR-6222U |
| Description | TDR; 0.05 s...100 h; Single Shot Falling Edge; 24-240V AC & 12-125V DC |
| Datasheet | Download Datasheet |
The Macromatic TR-6222U is a time delay relay with 2C DPDT output and rated 10 A at 240 V AC, 10 A at 30 V DC, driven by a 24-240V AC & 12-125V DC input.
It is adjustable from 0.05 s to 100 h, over sixteen selectable scales and set by a rotary range switch and knob.
It is a Single Shot Falling Edge timer.
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output remains de-energized. Upon removal of the trigger, the output is energized and the time delay (t) begins. At the end of the time delay (t), the output is de-energized unless the trigger is removed and re-applied prior to time out (before time delay (t) elapses). Continuous cycling of the trigger at a rate faster than the time delay (t) will cause the output to remain energized indefinitely.
It is started by a control switch.
It has Socketable mounting and Plug In terminals.
| Category | |
| Manufacturer | Macromatic |
| Model | TR-6 |
| Output Technology | Electromechanical Relay |
| Timing Function | Single Shot Falling Edge |
| Delay Time | 0.05 s...100 h |
| Time Ranges | A 0.05-0.5 s, B 0.1-1 s, C 0.5-5 s, D 1-10 s, E 3-30 s, F 6-60 s, G 0.2-2 min, H 0.5-5 min, I 1-10 min, J 3-30 min, K 6-60 min, L 0.2-2 h, M 0.5-5 h, N 1-10 h, O 2.4-24 h, P 10-100 h |
| Timing Adjustment Method | Rotary range switch and knob |
| Timing Initiate Method | Control Switch |
| Contact Configuration | 2C DPDT |
| Output Rating | 10 A at 240 V AC, 10 A at 30 V DC |
| Pilot Duty | B300 & R300; AC15 & DC13 |
| Input Voltage | 24-240V AC & 12-125V DC |
| Termination Style | Plug In |
| Mounting Type | Socketable |
| Socket Family | 11 Pin Octal |
| Required Socket | 70170-D |
| Operating Temperature | -28...+65 °C (-40...+85 °C) |
| Approvals | UL Recognized (E109466), CE |
| Setting Accuracy (%) | Maximum setting +5%/-0%, minimum setting +0%/-50% |
| Repeatability (%) | +0.1% or +50 ms, whichever is greater, at constant voltage and temperature |
| Start-Up Time | 0.05 s |
| Maintain Function Time | 0.01 s |
| Mechanical Life | 10,000,000 cycles (100,000 cycles) |
| Input Operating Range | 20.4...264 V AC at 50/60 Hz, 10.2...137.5 V DC |
| Rated Power | 3 VA |