Product Attribute
| Attribute Value
|
| Type | Reversal, Loss, Unbalance, Voltage |
| Coil Voltage | 190-500V |
| Contact Configuration | 1C SPDT |
| Mounting | 8 Pin Plug-in |
| Contact Current | 10 Amps |
| Min Voltage | 156V AC |
| Max Voltage | 550V AC |
| Three-Phase Line-Line Voltage | The Voltage Line-Line knob on the PMPU-FA8 has two ranges (left): a 190-250V low voltage scale and a 380-500V high voltage scale. The unit auto senses the 3-phase line-line voltage when applied and automatically selects the appropriate range. |
| Power Consumption | Less than 40VA. |
| Phase Loss | Unit trips on loss of any Phase A, B or C, regardless of any regenerative voltages. |
| Phase Reversal (Out-of-Sequence) | Unit trips if sequence (rotation) of the three phases is anything other than A-B-C. It will not work on C-B-A. |
| Undervoltage | Fixed at 90% of the line voltage setting. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the fixed 4 second trip delay. It will reset at +3% of the Undervoltage trip setting. |
| Overvoltage | Fixed at 110% of the line voltage setting. Unit trips when the average of all three lines is greater than the fixed set point for a period longer than the fixed 4 second trip delay. It will reset at 107% of the line voltage setting. |
| Phase Unbalance | Fixed at 6% unbalance. Unit trips when any one of the three lines deviates from the average of all three lines by more than the adjusted set point for a period longer than the fixed 4 second trip delay. |
| Response Times | See Datasheet |
| Output Contacts | SPDT 10A @ 277V AC / 7A @ 30V DC; 1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty |
| Life | Mechanical: 10,000,000 operations; Full Load: 100,000 operations |
| Temperature | Operating: -28o to 65oC (-18o to 149oF); Storage: -40o to 85oC (-40o to 185oF) |
| Mounting | Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V such as Macromatic Catalog Number 70169-D. |
| Reset | As standard, the PMPU-FA Series relays are in the Automatic Reset mode. However, they can be set in the Manual Reset mode by connecting an external N.C. switch across terminals 6 and 7. Upon application of line voltage, the PMPU-FA8 Series will go into Manual Reset mode if it recognizes a closure across terminals 6 and 7. After a fault clears, the relay will not reset until the N.C. switch is opened. Note: When the unit is in the Manual Reset mode, the N.C. switch must be opened after each Power-up to reset the relay and resume normal operation. |