Product Description
Description: Phase Monitor Relays • Type: Reversal, Loss, Unbalance, Voltage • Coil Voltage: 460-600 VAC • Contact Configuration: 1C SPDT • Mounting: 8 Pin Plug-in • Contact Current: 10 Amps
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Type | Reversal, Loss, Unbalance, Voltage |
Coil Voltage | 460-600 VAC |
Contact Configuration | 1C SPDT |
Mounting | 8 Pin Plug-in |
Contact Current | 10 Amps |
Hysteresis | 2 - 3% |
Indicator LED | See Datasheet |
Life | Mechanical: 10,000,000 operations, Full Load: 100,000 operations |
Load (Burden) | Less than 3VA |
Mounting | Uses an Plug-in 8 Pin Octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic Product Number 70169-D--see Page 16 of Catalog). |
Output Contacts | SPDT: 10A Resistive @ 240V AC/30V DC, 1/2HP @ 120/240V AC |
Overvoltage | Fixed at 110% of nominal voltage. Unit trips when the average of all three lines is greater than the fixed set point for a period longer than the time delay drop-out. |
Phase Loss | Unit trips on loss of any Phase A, B or C. |
Phase Reversal | Unit trips if rotation (sequence) of the three phases is anything other than A-B-C |
Phase Unbalance | Adjustable from 2 - 10% unbalance. Unit trips when any one of the three lines deviates from the average of all three lines by more than the adjusted set point . There is also a 'Disable' setting adjustment that will turn off the Phase Unbalance Protection if nuisance tripping is a problem. |
Reset | As standard, reset is automatic upon correction of fault. When a momentary-contact N.C. switch is wired across the Manual Reset terminals (6 & 7), the unit switches to manual reset mode and remote manual reset is available. |
Response Times | See Datasheet |
Temperature | -28° to 65°C (-20° to 150°F) |
Transient Protection | n/a |
Undervoltage | Adjustable from 80-95% of nominal voltage. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the adjustable time delay drop-out. |
Series Features |
PMP Series PHASE LOSS, PHASE REVERSAL, PHASE UNBALANCE, UNDERVOLTAGE & OVERVOLTAGE |
Series Description: The PMP Series Three-Phase Monitor Relays continuously monitor all voltages to protect motors and equipment from expensive damage due to phase loss, phase reversal, phase unbalance, undervoltage and overvoltage. These products detect single phasing and unbalanced voltages regardless of any regenerative voltages. Utilizing an advanced microprocessor-based design allows true RMS voltage measurement with full wave monitoring. This provides a more accurate method to measure the voltages, regardless of load type or wave shape, and results in improved protection across more applications. True RMS voltage measurement ensures accurate sensing in most generator and other applications with non-sinusoidal wave forms, eliminating nuisance tripping. Full wave monitoring provides a more accurate method to measure the voltages, regardless of load type or wave shape, resulting in improved protection across more applications. Unlike similar three-phase monitor relays, the PMP Series will continue to function even with a lost phase. They are the only line-powered units in their class to retain fault indication and continuous monitoring of all voltages during a phase loss, increasing the ease of troubleshooting and the level of protection. The PMP Series is a true universal product, with three units that work on a wide variety of adjustable line-line voltages to cover more global applications. Additional knobs allow adjustment of the undervoltage trip point, trip delay, restart delay and unbalance trip point. They utilize an industry-standard 8 pin octal socket. |
Operation: 10A SPDT output contacts |
|