Product Attribute
| Attribute Value
|
| Type | Reversal, Loss, Unbalance, Voltage |
| Coil Voltage | 102-138V |
| Contact Configuration | 2C DPDT |
| Mounting | Din Rail / Panel Mount |
| Contact Current | 10 Amps |
| Indicator LED | See Datasheet |
| Min Voltage | 77V AC |
| Max Voltage | 152V AC |
| Three-Phase Line-Line Voltage | The Voltage Line-Line knob on the PMDU has two ranges (right): a 190-250V low voltage scale and a 380-500V high voltage scale. The unit auto senses the three-phase line-line voltage when applied and automatically selects the appropriate range.
The PMD120 has a single adjustable range of 102-138V and the PMD575 has a single adjustable range of 460-600V. |
| Power Consumption | Less than 40VA. |
| Phase Loss | Unit trips on loss of any Phase A, B or C, regardless of any regenerative voltages. |
| Phase Reversal (Out-of-Sequence) | Unit trips if sequence (rotation) of the three phases is anything other than A-B-C. It will not work on C-B-A. |
| Undervoltage | Adjustable from 80-95% of the line voltage setting. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the adjustable trip delay. It will reset at +3% of the Undervoltage trip setting. |
| Overvoltage | Fixed at 110% of the line voltage setting. Unit trips when the average of all three lines is greater than the fixed set point for a period longer than the adjustable trip delay. It will reset at 107% of the line voltage setting. |
| Phase Unbalance | Adjustable from 2 - 10% unbalance. Unit trips when any one of the three lines deviates from the average of all three lines by more than the adjusted set point for a period longer than the adjustable trip delay. |
| Response Times | See Datasheet |
| Output Contacts | DPDT 10 A @ 277V AC / 10A @ 30V DC; 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.), B300 Pilot Duty, R300 (N.O.) |
| Life | Mechanical: 10,000,000 operations; Full Load: 100,000 operations |
| Temperature | Operating: -28o to 65oC (-18o to 149oF); Storage: -40o to 85oC (-40o to 185oF) |
| Mounting | Mounts on 35mm DIN-rail or panel-mounted with two #8 screws when DIN-rail clips are fully extended from under the enclosure. |
| Reset | As standard, the PMD Series relays are in the Automatic Reset mode. However, they can be set in the Manual Reset mode by connecting an external N.C. switch across terminals 4 and 5. Upon application of line voltage, the PMD Series will go into Manual Reset mode if it recognizes a closure across terminals 4 and 5. After a fault clears, the relay will not reset until the N.C. switch is opened. Note: When the unit is in the Manual Reset mode, the N.C. switch must be opened after each Power-up to reset the relay and resume normal operation. |
| Termination | Cage-clamp screw terminals Plus-minus screws accept flat and phillips head tools Recommended tightening torque of 7 in-lbs; Accepts solid or stranded wire 12-30 AWG |