Phase Monitor Relay • Type: Reversal, Loss, Undervoltage • Coil Voltage: 480 V • Contact Configuration: 1C SPDT • Mounting: 8 Pin Plug-in • Contact Current: 10 Amps • Indicator LED: Red LED on when all conditions are normal, and off when a fault condition has occurred • Under-Voltage Range: 360-460V
Red LED on when all conditions are normal, and off when a fault condition has occurred
Under-Voltage Range
360-460V
Life
Full Load: 100,000 operations
Load (Burden)
3VA
Mounting
Uses an Plug-in 8 Pin Octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic Product Number 70169-D--see Page 16 of Catalog).
Output Contacts
10A SPDT @ 240V AC, 1/3HP @ 240V AC (N.O.), 1/6HP @ 240V AC (N.C.)
Phase Loss
Unit trips on loss of any Phase A, B or C
Phase Reversal
Unit trips if sequence of the three phases is anything other than A-B-C.
Reset
Automatic upon correction of fault
Response Times
Operate: 50ms, Release: 50ms
Temperature
-28° to 65°C (-20° to 150°F)
Transient Protection
10,000 volts for 20 microseconds
Undervoltage
Adjustable over a range per product selection table. Unit trips when the average of all three lines is less than the adjusted set point
Series Features
PAP Series PHASE LOSS, PHASE REVERSAL & UNDERVOLTAGE
Series Description:The PAP Series Three-Phase Monitor Relays continuously monitor all voltages to protect motors and equipment from expensive damage due to phase loss, phase reversal and undervoltage. These products detect single phasing and unbalanced voltages regardless of any regenerative voltages.
Utilizing an advanced microprocessor-based design allows true RMS voltage measurement with full wave monitoring. This provides a more accurate method to measure the voltages, regardless of load type or wave shape, and results in improved protection across more applications.
True RMS voltage measurement ensures accurate sensing in most generator and other applications with non-sinusoidal wave forms, eliminating nuisance tripping. Full wave monitoring provides a more accurate method to measure the voltages, regardless of load type or wave shape, resulting in improved protection across more applications.
Unlike similar three-phase monitor relays, the PAP Series will continue to function even with a lost phase. They are the only line-powered units in their class to retain fault indication and continuous monitoring of all voltages during a phase loss, increasing the ease of troubleshooting and the level of protection.
The PAP Series have an adjustable undervoltage trip point of 75-95% of the line- line voltage setting. They utilize an industry-standard 8 pin octal socket.
Operation:
Protects against phase loss, phase reversal & undervoltage
True RMS voltage measurement ensures accurate sensing across more applications
Retains fault indication and continues monitoring all voltages even with a lost phase
Full fault indication on top of unit for easy troubleshooting