Operating configuration applied to single channel relays
Control Voltage
120 VAC
Number of Channels
1
Mounting
8 Pin Plug-In
Contact Configuration
1A SPST-NO
Load (Burden)
1.25 VA
Input Switch Open Circuit Voltage
6V DC
Output Contacts
10A @ 120V AC Resistive
Life
Mechanical: 10,000,000 operations Full Load: 100,000 operations
Response Times
Operate: 11ms Release: 4ms
Operating Temperature
-20o to + 60o C (-4 F to +140o F)
Storage Temperature
-45o to +85o C (-49o to 185o F)
Insulation Voltage
2000 volts (between coil and contacts)
LED Indicator
Green ON when output contact is closed and OFF when output contact is open.
Mounting
The socket can be both mounted on 35 mm DIN Rail or panel-mounted with two #8 screws
Series Features
ISP Series PLUG-IN INTRINSICALLY SAFE BARRIER RELAYS
Series Description:The ISP Series of Intrinsically Safe Barrier Relays provide a safe and reliable method to control a single load (motor starters, relays, etc.) with a single input device (switches, sensors, etc.) located in a hazardous area.
The ISP Series relay must be installed following Macromatic Control Drawing Number ISR2A01D as shown in Instruction Sheet 901-0000-260.
The ISP Series relays utilize an 8 pin plug-in design with socket (included) that can be both mounted on 35mm DIN rail or panel-mounted with two screws.
Operation:LED status indicator
Approved for use in these Hazardous Locations: Class III, Div 1
1-Channel
Terminals support 2-wire inputs
Input voltage of 120V AC
Isolated 10A relay output
Plug-in design for easy installation and replacement