Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Macromatic |
| Manufacturer Product Number | THS-1654D-32T |
| Description | Time Delay Relay; 0.1...10 min; Trig. Delayed Interval; 12-125V DC; 1-Pin Trigger |
| Datasheet | Download Datasheet |
The Macromatic THS-1654D-32T is a time delay relay with 1A SPST-NO output and rated 1 A continuous, 10 A inrush at 65 °C, pilot duty, driven by a 12-125V DC input.
It is adjustable from 0.1 to 10 min and set by an onboard knob.
It is a Delayed Interval (Switch Trigger) timer.
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the relay is ready to accept another trigger. During both time delay (t1) & time delay (t2), the trigger is ignored.
It is started by a control switch.
Build option: control switch common to pin 2 (single-pin trigger).
It has Surface Mounting and 0.250" (6.3mm) quick-connect terminals.
| Category | |
| Manufacturer | Macromatic |
| Model | THS-1 |
| Output Technology | Solid State |
| Timing Function | Delayed Interval (Switch Trigger) |
| Delay Time | 0.1...10 min |
| Timing Adjustment Method | Onboard knob |
| Options | Control switch common to pin 2 (single-pin trigger) |
| Timing Initiate Method | Control Switch |
| Contact Configuration | 1A SPST-NO |
| Output Rating | 1 A continuous, 10 A inrush at 65 °C, pilot duty |
| Input Voltage | 12-125V DC |
| Termination Style | Quick Connect - 0.250" (6.3mm) |
| Mounting Type | Surface Mount |
| Operating Temperature | -28...+65 °C (-40...+85 °C) |
| Approvals | UL Recognized (E236146) |
| Setting Accuracy (%) | Maximum setting +5%/-0%, minimum setting +0%/-50% |
| Repeatability (%) | +0.1% or +0.04 s, whichever is greater, at constant voltage and temperature |
| Start-Up Time | 0.05 s |
| Maintain Function Time | 0.01 s |
| Input Operating Range | +10%/-15% of nominal, AC at 50/60 Hz and DC |
| Rated Power | 1 VA |