| Manufacturer | Macromatic |
| Manufacturer Product Number | THS-1414A-35T |
| Description | Time Delay Relay; 1...100 h; Trig. On Delay/Off Delay; 24-240V AC; 1-Pin Trigger |
| Datasheet | Download Datasheet |
The Macromatic THS-1414A-35T is a time delay relay with 1A SPST-NO output and rated 1 A continuous, 10 A inrush at 65 °C, pilot duty, driven by a 24-240V AC input.
It is adjustable from 1 to 100 h and set by an onboard knob.
It is an On Delay / Off Delay (Switch Trigger) timer.
Upon application of control voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the trigger is removed, the output contacts remain energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the time delay relay is ready to accept another trigger. If the trigger is removed during time delay period (t1), the output will remain de-energized and time delay (t1) will reset. If the trigger is re-applied during time delay period (t2), the output will remain energized and the time delay (t2) will reset.
It is started by a control switch.
Build option: control switch common to pin 2 (single-pin trigger).
It has Surface Mounting and 0.250" (6.3mm) quick-connect terminals.
| Category | |
| Manufacturer | Macromatic |
| Model | THS-1 |
| Output Technology | Solid State |
| Timing Function | On Delay / Off Delay (Switch Trigger) |
| Delay Time | 1...100 h |
| Timing Adjustment Method | Onboard knob |
| Options | Control switch common to pin 2 (single-pin trigger) |
| Timing Initiate Method | Control Switch |
| Contact Configuration | 1A SPST-NO |
| Output Rating | 1 A continuous, 10 A inrush at 65 °C, pilot duty |
| Input Voltage | 24-240V AC |
| Termination Style | Quick Connect - 0.250" (6.3mm) |
| Mounting Type | Surface Mount |
| Operating Temperature | -28...+65 °C (-40...+85 °C) |
| Approvals | UL Recognized (E236146) |
| Setting Accuracy (%) | Maximum setting +5%/-0%, minimum setting +0%/-50% |
| Repeatability (%) | +0.1% or +0.04 s, whichever is greater, at constant voltage and temperature |
| Start-Up Time | 0.05 s |
| Maintain Function Time | 0.01 s |
| Input Operating Range | +10%/-15% of nominal, AC at 50/60 Hz and DC |
| Rated Power | 1 VA |