Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Type | Overcurrent, Undercurrent & Band |
Coil Voltage | 24-240 VAC/DC |
Contact Configuration | 2C DPDT |
Mounting | Din-Rail |
Current Range Monitored | 5mA-100mA, 0.05A-1A, 0.5A-10A |
Indicator LED | Green ON: Control Voltage is applied; Green LED flashes: Start-up suppression delay; Yellow ON: Relay output ON; Red ON: Corresponding threshold exceeded; Red flashes: Tripping delay |
Response Times | Pick-up <= 100 ms, Drop-out Adjustable, 0.1-10s |
Output Contact | 5A@250V AC, 5A@24V DC, B300 Pilot Duty |
Life | Mechanical: 20,000,000 operations Full Load: 200,000 operations at 1000VA resistive load. |
Temperature | Operating: -25o to 55o C (-13o to 131o F) Storage: -25o to 70o C (-13o to 158o F) |
Mounting | Compact 22.5 mm wide enclosure mounts on 35mm DIN-rail |
Series Features |
OVERCURRENT, UNDERCURRENT & BAND (WINDOW) CMD Series |
Series Description: CMD Series Current Sensing Relays monitor current conditions to protect equipment and critical processes, reducing downtime and extending operating life. Model CMD10AD2U monitors single phase AC and DC current to protect against overcurrent and undercurrent fault conditions. A band (window) function can protect equipment that is required to operate within a maximum and minimum current limit. Each function can be set to operate in latch mode. See “Latching Operation” on page 9. Separate adjustment dials allow selecting the maximum threshold (MAX), minimum threshold (MIN), tripping delay(Delay), and start-up sensing delay (Start). The relays are typically used to detect conveyor jam-up conditions, machine tool wear, no load conditions, HVAC system status, and heater |
|