Product Description
Description: Current Monitor Relays • Type: Overcurrent • Coil Voltage: 24 VAC • Contact Configuration : 1C SPDT • Mounting: 11 Pin Plug-in • Current Range Monitored: See Data Sheet • Indicator LED: Green when Input Voltage is applied; Red when Relay is energized
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Type | Overcurrent |
Coil Voltage | 24 VAC |
Contact Configuration | 1C SPDT |
Mounting | 11 Pin Plug-in |
Current Range Monitored | See Data Sheet |
Indicator LED | Green when Input Voltage is applied; Red when Relay is energized |
Input Voltage Tolerance | +10/-15% of nominal at 50/60 Hz. |
Load (Burden) | Less than 5VA |
Current Settings | Pick-up (Threshold): Adjustable throughout monitored current range Drop-out (Hysteresis): Adjustable from 5-50% below pick-up setting |
Response Times | Pick-up & Drop-out: Fixed 100ms; Sensing delay on power-up (ts): 0.1 10 seconds |
Output Contacts | 10A@240VAC/7A@28VDCSPDT,1/4HP@120VAC(N.O.) |
Life | Mechanical: 10,000,000 operations Full Load: 100,000 operations |
Temperature: Operating | -28o to 55o C (-18o to 131o F) Storage: -40o to 85o C (-40o to 185o F) |
Mounting | Requires an 11 pin octal socket (Macromatic 70170-D) that can be mounted on 35mm DIN rail or panel-mounted with two screws |
Series Features |
CAP Series AC/DC Overcurrent |
Series Description: The CAP Series current sensing relay is used to detect an AC or DC overcurrent condition. It has two operating modes: non-latching or latching. Each relay has three top-mounted potentiometers: one for selecting the pick-up setting within the selected monitored current range (Threshold), one for selecting the drop-out setting of 5-50% below pick-up setting (Hysteresis), and one for setting the start- up sensing delay (ts). This delay, which is adjustable from 0.1 10 seconds, inhibits energization of the output relay during the start-up period. CAP Series relays have three built-in current ranges (see right) to monitor both AC & DC current. Each one is easily selectable by connecting to the corresponding terminal and to the COM terminal (see Wiring Diagram below) Non-Latching Mode: The unit will operate in the non-latching mode if no circuit is completed across pins 9 & 11. After input voltage is applied (LED is Green) and the start-up sensing delay (ts) of 0.1 10 seconds is completed, the relay will energize when the monitored current is above the adjustable pick-up setting (Threshold). The LED will be Red. It will de-energize when the monitored current goes below the adjustable drop-out setting (Hysteresis) by 5-50% of the selected pick-up setting or when input voltage is removed. The LED will be Green. Latching Mode: The unit will operate in the latching mode if a N.C. contact (Memory S2) is connected across pins 9 & 11 (see Wiring Diagram). After input voltage is applied (LED is Green) and the start-up sensing delay (ts) of 0.1 10 seconds is completed, the relay will energize when the monitored current is above the adjustable pick-up setting (Threshold). The LED will be Red. It will de-energize when the monitored current goes below the adjustable drop-out setting (Hysteresis) by 5-50% of the selected pick-up setting and the N.C. contact (Memory S2) is opened, or when input voltage is removed. The LED will be Green. It is recommended to set the Hysteresis at 5% when in the latching mode. |
|