Mechanical: 10,000,000 operations • Full Load: 100,000 operations
Load (Burden)
Less than 3VA
Optional Selector Switch Settings
LOAD 1 ALTERNATE LOAD 2
Output Contacts
10A @ 240V AC/24V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240VAC (N.C.) B300, R300 (N.O.) Pilot Duty
Temperature
Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF)
Voltage Tolerances
AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal.
Series Features
ARF Series SPDT & DPDT CROSS-WIRED DUPLEXOR
Series Description:Alternating Relays are used in applications requiring the optimization of load usage by equalizing the run time of two loads. A version with DPDT Cross-Wired output is also used for additional capacity in case of excess load requirements. This alternating action is initiated by a control switch, such as a float switch, manual switch, timing relay, pressure switch, or other isolated contact. Each time the initiating switch is opened, the output relay contacts will change state, thus alternating the two loads.
A three-position selector switch is included. For SPDT versions, this allows the unit to alternate the two loads as normal or select one or the other load to be the only one energized when the control switch closes. For DPDT cross-wired versions, the switch provides the option to alternate the two loads as normal or select which load always comes on first when the LEAD switch closes. In either case, a load that has fewer hours of operation than the other load could be used more often to eventually balance the run time of both loads. The low-profile selector switch prevents any accidental changes in status.
These products utilize a flange-enclosure designed to be deadfront-mount- ed on an inner door and used with back-mounted sockets. Everything need- ed for setup, use and troubleshooting is on the top of the unit: LED status indication and low-profile selector switch. With this product, the selector switch can be moved to any position without having to open the inner door.
For Duplex Control of two loads
Both SPDT Output & DPDT Cross-Wired Output
Control voltages of 12 & 24V AC/DC and 120 & 240V AC
Flange-enclosure designed for deadfront door-mounting
Low profile selector switch for normal alternation or to lock either load ON first
Selector switch accessible without opening inner door