50 / 60 (50 will increase all delay timers by 20%)
Output Form
SPDT - 1 Form C
Output Load Rating (VA)
Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac
Restart Delay Range
Undervoltage: 2 s; Complete Power Loss: 2 s
Trip Delay Range
2 - 30 s
Undervoltage Trip Voltage
0.9
Undervoltage Reset Voltage (%)
0.93
Termination Type
Torque: 7 in-lbs; Wire Size: 12 - 18 AWG
Mounting Method
#8 screws
Operating Temperature
-20° to 70°C (-4° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Humidity
10 - 95% non-condensing per IEC 68-2-3
Dimensions
2.93 H x 5.27 W x 2.95 D in. (74.4 x 133.9 x 74.9 mm)
Series Features
50R Series - Single-Phase Voltage Monitor
Series Description:The 50R series is a single-phase voltage monitor with a voltage-sensing circuit that constantly monitors the single-phase power for a low-voltage condition. When a harmful condition is detected, the MotorSaver® deactivates its output relay after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions. This monitor is used in a variety of applications such as compressors, air conditioners, heat pumps, well pumps, sump pumps, and small conveyer motors.
Series Applications:Fan motors, Air conditioners, Compressors, Heat, well, and sump pumps, Small conveyer motors
Proprietary voltage sensing circuitry: Constant monitoring of single-phase power for a low-voltage condition
Adjustable trip delay (-3 models) and restart delay (-2 models) settings: Prevents nuisance tripping due to rapidly fluctuating power line conditions, allows staggered start-up of multiple motors after a fault
High-voltage detection (-9 models): Trips and resets at a fixed percentage of the setpoint: trip 110%, reset 107%
600 V rated relay contacts available on some models: Eliminates the need for a control transformer to step voltage down to 120–240 V for a control circuit