Product Description
Description: 3-Phase VM/190-480V/adj.VUB,TD,RD/DIN rail/Man.Res
| Product Information | Resources | 
| 
 | 
 | 
| Specifications | 
| Product Attribute | Attribute Value | 
| Input Voltage (V) | 190 - 480 Vac | 
| Maximum Input Power | 6 | 
| Input AC Line Frequency (Hz) | 50 / 60 (50 will increase all delay timers by 20%) | 
| Output Form | Form C | 
| Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac | 
| Restart Delay Range | 1 - 500 s adjustable | 
| Trip Delay Range | Under/Over and Unbalance Voltage: 1 - 30 s adjustable; single-Phase faults (>25%UB): 1 s fixed | 
| Trip Point Accuracy (%) | ±1% | 
| Overvoltage Trip Voltage (%) | 1.1 | 
| Overvoltage Reset Voltage (%) | 1.07 | 
| Undervoltage Trip Voltage | 0.9 | 
| Undervoltage Reset Voltage (%) | 0.93 | 
| Voltage Unbalance Trip Point (%) | 2 - 8% adjustable | 
| Voltage Unbalance Reset (%) | Trip setting minus 1% (5 - 8%); Trip setting minute 0.5% (2 - 4%) | 
| Protection Class | IP20; NEMA 1 (finger safe) | 
| Termination Type | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal | 
| Mounting Method | 35mm DIN rail or Surface Mount (#6 or #8 screws) | 
| Operating Temperature | -20° to 70°C (-4° to 158°F) | 
| Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) | 
| Humidity | 10 - 95% non-condensing per IEC 68-2-3 | 
| Dimensions | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) | 
| Series Features | 
| 460 SERIES - 3-Phase Voltage Monitor | 
| Series Description: The 460 is a 3-phase voltage monitor that protects 190-480VAC or 475-600V, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically senses line voltage. This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions such as low, high, and unbalanced voltage, loss of any phase, and phase reversal. When a harmful condition is detected, the MotorSaver® output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (restart delay). The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions. All 460 models feature adjustable 1-30 second trip delay, 1-500 second restart delay, 2-8% voltage unbalance trip point, and one form C contact except where noted below. | 
| 
 | 
 
             
                         
            