Product Description
Description: 3-Phase VM/475-600V/1 NO & 1 NC Relay
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 475 - 600 Vac |
Maximum Input Power | 6 |
Input AC Line Frequency (Hz) | 50 / 60 (50 will increase all delay timers by 20%) |
Output Form | 1 Form A and 1 Form B |
Output Load Rating (VA) | Pilot Duty: 360 VA @ 240 Vac B300; General Purpose: 8 A @ 240 Vac |
Restart Delay Range | 1 - 500 s adjustable |
Trip Delay Range | Under/Over and Unbalance Voltage: 1 - 30 s adjustable; single-Phase faults (>25%UB): 1 s fixed |
Trip Point Accuracy (%) | ±1% |
Overvoltage Trip Voltage (%) | 1.1 |
Overvoltage Reset Voltage (%) | 1.07 |
Undervoltage Trip Voltage | 0.9 |
Undervoltage Reset Voltage (%) | 0.93 |
Voltage Unbalance Trip Point (%) | 2 - 8% adjustable |
Voltage Unbalance Reset (%) | Trip setting minus 1% (5 - 8%); Trip setting minute 0.5% (2 - 4%) |
Protection Class | IP20; NEMA 1 (finger safe) |
Termination Type | Torque: 6 in-lbs; Wire: Stranded or solid 12 - 20 AWG one per terminal |
Mounting Method | 35mm DIN rail or Surface Mount (#6 or #8 screws) |
Operating Temperature | -20° to 70°C (-4° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm) |
Series Features |
460 SERIES - 3-Phase Voltage Monitor |
Series Description: The 460 is a 3-phase voltage monitor that protects 190-480VAC or 475-600V, 50/60Hz motors regardless of size. The product provides a user selectable nominal voltage setpoint and the voltage monitor automatically senses line voltage. This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions such as low, high, and unbalanced voltage, loss of any phase, and phase reversal. When a harmful condition is detected, the MotorSaver® output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (restart delay). The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions. All 460 models feature adjustable 1-30 second trip delay, 1-500 second restart delay, 2-8% voltage unbalance trip point, and one form C contact except where noted below. |
|