Product Description
Description: 1-Phase Voltage Monitor/190-240V/adj.RD
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 190 - 240 Vac |
Input Tolerance (%) | ±10% |
Maximum Input Power | 5 |
Input AC Line Frequency (Hz) | 50 / 60 (50 will increase all delay timers by 20%) |
Output Form | SPDT |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac |
Restart Delay Range | After a Fault or Complete Power Loss: Manual; 2 - 300 s adjustable |
Trip Delay Range | Under/Over Voltage: 4 s |
Trip Point Accuracy (%) | ±1% |
Overvoltage Trip Voltage (%) | 1.1 |
Overvoltage Reset Voltage (%) | 1.07 |
Undervoltage Trip Voltage | 0.9 |
Undervoltage Reset Voltage (%) | 0.93 |
Termination Type | 0.25 in male quick connect |
Mounting Method | 1/4 in socket head cap screw (customer supplied) |
Operating Temperature | -40° to 70°C (-40° to 158°F) |
Humidity | 95% non-condensing |
Dimensions | 2.5 H x 2.5 W x 1.4 D in. (63.5 x 63.5 x 35.6 mm) |
Series Features |
202-200-SP SERIES - Single-phase voltage monitor |
Series Description: The 202-200-SP Series voltage monitor is designed to protect single-phase motors regardless of size. It can be used with 190V-240VAC, 50/60Hz motors to prevent damage caused by incoming power problems. A unique microcontroller-based voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSavers output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions. |
|