Product Description
Description: 3-Phase Plug-in Voltage Monitor/190-480V/HV detect
| Product Information | | Resources |
| Manufacturer | Littelfuse - Symcom | | Product Category | Monitors | | Product Sub Category | Voltage Monitor Relays | | Series | 201A Series |
| | |
Product Attribute
| Attribute Value
|
| Input Voltage (V) | 190 - 480 Vac |
| Maximum Input Power | 5 |
| Input AC Line Frequency (Hz) | 50 / 60 |
| Output Form | SPDT |
| Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac |
| Restart Delay Range | 2 s |
| Trip Delay Range | Under/Over Voltage: 4 s; Unbalance/Phase faults: 2 s |
| Trip Point Accuracy (%) | ±1% |
| Overvoltage Trip Voltage (%) | 1.1 |
| Overvoltage Reset Voltage (%) | 1.07 |
| Undervoltage Trip Voltage | 0.9 |
| Undervoltage Reset Voltage (%) | 0.93 |
| Voltage Unbalance Trip Point (%) | 0.06 |
| Voltage Unbalance Reset (%) | 0.045 |
| Type of Detection | High Voltage Detection |
| Termination Type | Torque: 12 in-lbs.; 12 - 22 AWG solid or stranded |
| Mounting Method | DIN rail or surface mount (plug into OT08-PC socket) |
| Operating Temperature | -20° to 70°C (-4° to 158°F) |
| Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
| Dimensions | 1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm) |
| 201A Series - 3-Phase Voltage/Phase Monitor |
| Series Description: The 201A series is a three-phase, auto-ranging, dual-range voltage monitor that protects 190–480 V ac, 50*/60 Hz motors regardless of their size. This monitor provides a user-selectable nominal voltage setpoint and will automatically select between the 200 V and 400 V range. It includes advanced, single LED diagnostics where color and light patterns distinguish between faults and normal conditions. This unique microcontroller-based voltage and phase-sensing unit constantly monitors the three-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels for a specified restart delay time. |
| Series Applications: Fan motors, Air conditioners, Compressors, Heat, well, and sump pumps, Small conveyer motors |
- Proprietary microcontroller-based circuitry: Constant monitoring of single-phase, low-voltage, voltage unbalance, phase reversal, power line conditions – high-voltage monitoring is optional
- Auto-sensing wide voltage range: Automatically senses system voltage between 190–480 V ac. Saves setup time
- Advanced LED diagnostics: LED indications include: normal operation, power-up restart delay, reverse-phase trip, unbalance/single-phase trip, high/low voltage trip
- Compact design for 8-pin; DIN-rail or surface mount: Allows flexibility in panel installation
|