Product Description
Description: 3-Phase Plug-in VM/475-600V/adj.VUB,TD & RD
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 475 - 600 Vac |
Maximum Input Power | 5 |
Input AC Line Frequency (Hz) | 50 / 60 |
Output Form | Form C |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac |
Restart Delay Range | Manual; 1 - 500 s adjustable |
Trip Delay Range | Under/Over and Unbalance Voltage: 1 - 30 s adjustable; single-Phase faults: 1 s fixed |
Trip Point Accuracy (%) | ±1% |
Overvoltage Trip Voltage (%) | 1.1 |
Overvoltage Reset Voltage (%) | 1.07 |
Undervoltage Trip Voltage | 0.9 |
Undervoltage Reset Voltage (%) | 0.93 |
Voltage Unbalance Trip Point (%) | 2 - 8% adjustable |
Voltage Unbalance Reset (%) | Trip setting minus 1% (5 - 8%); Trip setting minute 0.5% (2 - 4%) |
Mounting Method | DIN rail or surface mount (plug into OT08-PC socket) |
Operating Temperature | -40° to 70°C (-40° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm) |
Series Features |
201A-AU Series - 3-Phase Voltage/Phase Monitor |
Series Description: The 201A-AU series is a three-phase, auto-ranging, dual-range voltage monitor that protects 190480 V ac, 50/60 Hz motors regardless of their size. This monitor provides a user-selectable nominal voltage setpoint and will automatically select between the 200 V and 400 V range. Additional adjustment knobs allow the user to set a 130 second trip delay, a manual restart or 1500 second restart delay, and a 28% voltage unbalance trip point. It includes advanced, single LED diagnostics where color and light patterns distinguish between faults and normal conditions. This unique microcontroller- based voltage and phase-sensing unit constantly monitors the three-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels for a specified restart delay time (or manual reset). |
Series Applications: Fan motors, Air conditioners, Compressors, Heat, well, and sump pumps, Small conveyer motors |
|