50 / 60 (50 will increase all delay timers by 20%)
Output Form
SPDT
Output Load Rating (VA)
Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac
Restart Delay Range
After a Fault or Complete Power Loss: 2 s
Trip Delay Range
Under/Over Voltage: 4 s
Overvoltage Trip Voltage (%)
1.1
Overvoltage Reset Voltage (%)
1.07
Undervoltage Trip Voltage
0.9
Undervoltage Reset Voltage (%)
0.93
Termination Type
Torque: 12 in-lbs.; 12 - 22 AWG solid or stranded
Mounting Method
DIN rail or surface mount (plug into OT08-PC socket)
Operating Temperature
-40° to 70°C (-40° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Dimensions
1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm)
Series Features
201-XXX-SP SERIES - Single-phase voltage/phase monitor
Series Description:The 201-xxx-SP series is an 8-pin octal-base, plug-in voltage monitor designed to protect single-phase motors regardless of size. The 201-100-SP is used on 95–120 V ac, 50/60 Hz motors to prevent damage caused by low voltage. The 201-200-SP is used on 190–240 V ac, 50/60 Hz motors. The 201-200-SP-T-9 is a pin-for-pin replacement for a Time Mark® #260 series voltage monitor. High voltage protection is included in the 201-200-SP-T-9.
The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSaverÂ’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.
Proprietary microcontroller based circuitry: Constant monitoring of voltage to detect harmful power line conditions, even before the motor starts
Fixed trip delay 4 s: Prevents nuisance tripping due to rapidly fluctuating power line conditions
Advanced LED indication: Provides diagnostics which can be used for troubleshooting and to determine relay status
Compact design for 8-pin; DIN rail or surface mount: Allows flexibility in panel installation