Product Description
Description: 1-Phase Plug-in Voltage Monitor/190-240V
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 190 - 240 Vac |
Maximum Input Power | 5 |
Input AC Line Frequency (Hz) | 50 / 60 (50 will increase all delay timers by 20%) |
Output Form | SPDT |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac |
Restart Delay Range | After a Fault or Complete Power Loss: 2 s |
Trip Delay Range | Under Voltage Fault: 4 s |
Undervoltage Trip Voltage | 0.9 |
Undervoltage Reset Voltage (%) | 0.93 |
Termination Type | Torque: 12 in-lbs.; 12 - 22 AWG solid or stranded |
Mounting Method | DIN rail or surface mount (plug into OT08-PC socket) |
Operating Temperature | -40° to 70°C (-40° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm) |
Series Features |
201-XXX-SP SERIES - Single-phase voltage/phase monitor |
Series Description: The 201-xxx-SP series is an 8-pin octal-base, plug-in voltage monitor designed to protect single-phase motors regardless of size. The 201-100-SP is used on 95120 V ac, 50/60 Hz motors to prevent damage caused by low voltage. The 201-200-SP is used on 190240 V ac, 50/60 Hz motors. The 201-200-SP-T-9 is a pin-for-pin replacement for a Time Mark® #260 series voltage monitor. High voltage protection is included in the 201-200-SP-T-9. The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the MotorSavers output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions. |
|