Product Description
Description: 3-Ph OLR/200-480V/2-90FLA/Internal 0-Seq CT/Plus
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 200 - 480 Vac |
Maximum Input Power | 10 |
Input AC Line Frequency (Hz) | 50 / 60 |
Output Form | SPDT - Form C |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 10 A @ 240 Vac |
Full Load Amp Range (A) | 2 - 20 (looped conductors required); 20 - 90 direct |
Timing Accuracy (%) | ±0.5 s |
Rapid Cycle Timer (s) | 0 - 999 s |
Restart Delay Range | All faults except undercurrent: 2 - 500 m; Undercurrent: 2 - 500 m A (Automatic); # of Restarts: All faults except undercurrent: 0; 1; oc1; 2; oc2; 3; oc3; 4; oc4; A; ocA (Automatic); Undercurrent: 0; 1; 2; 3; 4; A (Automatic) |
Repeat Accuracy (%) | Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 A direct) |
Overvoltage Trip Voltage (%) | 172 - 528 V |
Undervoltage Trip Voltage | 170 - 524 V |
Voltage Unbalance Trip Point (%) | 2 - 25% or 999 (disabled) |
Voltage Accuracy (%) | ±1% |
Overcurrent Trip Point | 2 - 100A with proper looping |
Overcurrent Trip Class | 02 - 60; J02 - J60; L00 - L60; or OFF |
Undercurrent Trip Point | 0; 10 - 98 A with proper looping |
Undercurrent Trip Delay (s) | 2 - 999 s (standard) |
Current Unbalance Trip Point (%) | 2 - 50% or 999 (disabled) |
Current Accuracy (%) | ±3% (<100 A direct) |
Ground Fault Current Trip Point (A) | (1 - 10) MULT or OFF |
Ground Fault Trip Delay (s) | 0s (default) |
Ground Fault Accuracy (%) | ±15% |
Sensor Hole Size | Max conductor size: 0.65 in (with insulation) |
Short Circuit (kA) | 100 |
Surge Protection | IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground |
Protection Class | IP20 (finger safe) |
Pollution Degree | 3 |
CT Ratio | 44936 |
Address | COM: C00 - C07; RS485: A01 - A99 |
Termination Type | Torque: 7 in-lbs |
Mounting Method | Surface mount (4 - #8 screws) or DIN rail mount |
Operating Temperature | -20° to 70°C (-4° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm) |
Series Features |
777 Series - 3-Phase Current & Voltage Monitor |
Series Description: The 777 unit is a fully-programmable, electronic overload relay designed to protect any motor drawing 2-800 full load A (external CTs are required above 90 A). The 777 (family of products) is used for 3-phase, 200-480 V ac applications, with several specialized units for other voltage ranges and unique applications. Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application. Some unique applications include use with a Subtrol* equipped Franklin submersible motor to detect high motor temperatures and applications where a fast linear trip is required All of the overload relays provide unsurpassed protection by combining overload, voltage, phase loss and reversal, voltage and current unbalance, power monitoring, and underload based on current all in one package. For standalone applications, the units incorporate a 3-digit LED display that is used for programming, providing real-time operational information, and displaying diagnostic codes to aid in troubleshooting a fault condition. The units also feature a communications network port that can be used with communication modules listed in the 777 accessories section to form a Modbus, DeviceNet*, Profibus, or Ethernet network. Up to 99 units can be remotely monitored and controlled from a PC, PLC, or SCADA system, and data logging through a PC with the optional Solutions software. This capability allows for a simple, cost-effective way to meet new requirements for arc-flash safety. |
Series Applications: Conveyor systems, HVAC equipment, Saws and grinders, Fan motors |
|