Product Description
Description: 4-Ch Intrinsically-Safe Only Switch/120V
| Product Information | | Resources |
| Manufacturer | Littelfuse - Symcom | | Product Category | Relays | | Product Sub Category | Intrinsically Safe Relays | | Series | ISS-105 SERIES |
| | |
Product Attribute
| Attribute Value
|
| Input Voltage (V) | 120 Vac |
| Input Tolerance (%) | ±10% |
| Maximum Input Power | 5 |
| Input AC Line Frequency (Hz) | 50 / 60 (50 will increase all delay timers by 20%) |
| Input Logic | Input/Output Channels: 4 channels |
| Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 7 A @ 240 Vac |
| Debounce Time Delay (s) | 2 |
| Sense Voltage | 5 Vdc continuous (probe) |
| Intrinsically Safe Circuit Location | Division 1 and 2; Class I Groups A B C D; Class II Groups E F G; Class III |
| Protection Class | IP20 (finger safe) |
| Termination Type | Torque: 3.5 to 4.5 in-lbs (max. 6 in.-lbs); Wire: 12 - 20 AWG |
| Mounting Method | 35mm DIN rail or Surface Mount (#6 or #8 screws) |
| Operating Temperature | -40° to 55°C (-40° to 131°F) |
| Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
| Dimensions | 2.35 H x 3.7 W x 5.03 D in. (59.7 x 94.1 x 127.6 mm) |
| ISS-105 SERIES - Five-Channel Intrinsically Safe Switch |
Series Description: The ISS-105 is a “smart” five-channel intrinsically safe relay and pump controller. The ISS-105 can be configured for pump-up or pump-down applications or as a five-channel relay covering a wide variety of applications.
The ISS-105 has a long list of features that are needed for multiple pump applications and can indicate low, high and out-of-sequence alarms. If an out-of-sequence alarm occurs, the skipped pump(s) will be started as intended.
The Model ISS-105 can be set-up to do non-alternating control, alternating control and alternating control with one non-alternating pump. The non-alternating pump is intended for use with an emergency or jockey pump. The ISS-105 can start an emergency pump once every 50 cycles to keep it working freely. Using the built-in DIP switches, individual pumps can be disabled when taken out of service for repair or maintenance. |
- 5 intrinsically-safe input channels meeting UL913 Sixth Edition
- 4 normally open output relays and 1 SPDT output relay
- Field selectable pump control options
- Monitors float sequencing and sends signal to alarm if out-of-sequence condition occurs
- High and/or low alarm options depending on the number of pumps and settings
- Output contacts for audible alarm
- Meets IEC EMC standards for Electrical Fast Transients (EFT), Electrostatic Discharge (ESD) and Radio Frequency Immunity (RFI)
- DIN rail or surface mountable allows flexibility in panel installation User-selectable alternator/non-alternator option
- Non-alternating pump option for emergency or jockey applications
- Pump disable switches make it easy to disable individual pumps when they are out for service or repair
- Adjustable lag pump delay for all pumping modes
- Adjustable delay-on-make/break timer in five-channel relay mode
- Finger-safe terminals meet IEC 61000 safety requirements
|
Custom Field
short_description 4-Ch Intrinsically-Safe Only S